Function
23 / 121
2.2.7
Outputs
There are two OC outputs (OC
Flt
and OC
Al
) on the ASD 532. Parallel indicators, feedback indicators or other consumers (re-
lays) can be connected to these outputs. The outputs are configured with the following criteria (see also Sec. 6.6.5):
Unit
OC designation
Function, events
AMB 32
OC
Flt
Fault (all events) / ASD inactive
OC
Al
Smoke sensor alarm release
2.2.8
Inputs
The ASD 532 has an “
External reset
” input used to reset the device to its normal state after an event. The input is potential-
free (opto-isolator). It can be actuated both on the “plus” and on the “minus” side. The input operates in the 5 to 30 VDC range
and has a pulse bandwidth of 0.5 to 10 sec. When a continuous signal is applied for longer than 20 s, the ASD 532 is deacti-
vated (fault state) (see also Sec. 6.6.2). Switching inactive via the “Reset external” input works only if the ASD 532 is not
equipped with an XLM 35.
The “
OEM
” input is for actuating alarms and faults from third-party detectors. The input is potential-free (opto-isolator) and can
be actuated “plus” side or “minus” side in the range of 5 to 30 VDC. By default the input is not enabled and must be parameter-
ised using the “ASD Config” configuration software (OEM input signal). It actuates the alarm and fault states on the ASD (relay
+ LED). The same delay times and latching states as for triggering from the SSD 532 apply.
Warning
•
In some cases actuations via the OEM input may
not
comply with requirements
in accordance with EN 54-
20
and may therefore only be used after consulting with the manufacturer.
•
The input is
not
line monitored.
2.2.9
Interfaces
Depending on the installed additional modules, the ASD 532 has the following interfaces:
Unit
Designation
Function, events
AMB 32
Ethernet / TCP/IP
Configuration with “ASD Config”
Update of the firmware
SD memory card
Record operating data
Update of the firmware
XLM 35
L1 / C1 / G1 // L2 / C2 / G2
SecuriFire / Integral addressable loop
SIM 35
GND / D + / D –
RS485
ASD532
Operating
Manual