Function
21 / 121
2.2.4
Programming / operation
The operation of the ASD 532 aspirating smoke detector in normal mode (after commissioning) is limited to switching on/off or
to resetting a triggered event (alarm/fault). Operation is generally via the FACP, with input of the “Zone On/Off” and “Reset”
functions (on “Reset external” input of the ASD 532).
Events triggered on the ASD 532 can be reset locally using the “
Reset
” key on the control unit or by briefly actuating the “Re-
set External” input. The reset is possible only if the triggered event is no longer pending (e.g. smoke sensor no longer has
smoke). The application of a continuous signal at the “Reset external” input also deactivates (switches off) the ASD 532 (see
also Sec. 2.2.8 and 6.6.2).
Notice
A local reset does not reset a higher-order FACP. It may happen that the reset in the ASD 532 triggers a fault in
the superordinate line of the FACP.
To aid commissioning the ASD 532, there are two 7-segment displays, an alphanumeric display, and two keys (“UP” and “OK”)
inside the device on the AMB 32 Main Board. These elements provide a type of rotary switch function, i.e. displays and posi-
tions in the range
A00
to
Z99
may appear.
These elements are used when commissioning the ASD 532. Device settings for predefined system limits can also be called
up –
EasyConfig
. These pre-defined positions are stored with normative values for response sensitivity, airflow monitoring
(
LS-Ü
) and pipe configuration. They also contain positions which allow deviations from the normative limits with regard to air-
flow monitoring. The
EasyConfig
process allows the device to be commissioned without the ASD Config software. If system-
specific programming has to be carried out (e.g. after a calculation with “ASD PipeFlow” or when programming RIM 36), the
“ASD Config” configuration software must be used.
shows the workflow for defining and programming project-specific device functions.
Fig. 3 Workflow for project-related programming
Warning
Switch settings
W01
to
W44
may be used only after consulting with the manufacturer. The airflow monitoring val-
ues stored under those switch positions are
not
tested in accordance with EN 54-20.
The description of the predefined positions and the operator structure is found in Sec. 4.4.4.3, 4.4.4.4, 7.2.1 and 8.3.
yes
yes
no
no
Project-specific selection
of system limits acc. to
Sec. 4.4.4.3
Selection of the
appropriate switch setting
to
in the ASD
A11 C31
Selection of the
appropriate switch setting
to
in the ASD
W01 W44
Airflow monitoring
acc. to EN 54-20
Create and calculate
“ASD
”
Results compliant
with EN 54-20
PipeFlow
Enter result in
ASD
“
”
configuration software
Config
Select switch setting
,
or
in the ASD to save result
X01 X02
X03
Using
“ASD ”
PipeFlow
EasyConfig
ASD532
Operating
Manual