Installation
74 / 121
6.6.3
Control
The ASD 532 units connected to an FACP are controlled according to the detection zone mapping using the FACP states
“Zone On/Off” and “Reset”. Two possibilities are available:
•
Control via supply voltage (auxiliary relays in the ASD power supply line);
•
Control via the “Reset external” input
6.6.3.1
Control via voltage supply by means of auxiliary relay
Depending on the location of the ASD power supply, the auxil-
iary relay may be placed in the FACP or directly in the ASD
532.
The auxiliary relay can be actuated in the following ways (see
A.
line plus or minus
B.
SW output of the FACP
C.
SW output or function of a control module
The function types described above are determined by the
FACP technology used; it is therefore essential to contact the
manufacturer and/or the supplier of the FACP for details be-
fore implementing.
Danger
•
The EMC protective elements at the input of
the ASD electronics cause a brief current
peak (5 A / 1 ms) when the supply voltage is
applied. When using auxiliary relays with a
maximum contact rating of 1 A, this may lead
to the relay contact sticking. For this reason
auxiliary relays with a contact load of over
1 A
should
generally
be used, e.g. PMR 81 semi-
).
•
The ASD supply path routed via the auxiliary
relay contact must be short-circuit-proof or
routed via a fuse component (circuit-breaker
card).
Notice
•
When using a PMR 81 semi-conductor relay,
it may be necessary to invert the actuation
signal (PMR only has a normally open (NO)
contact function).
•
To guarantee comprehensive emergency run-
ning properties, the connection must in all
cases be implemented in such a way that if
there is an FACP computer failure the ASD
will continue to function (reset input not actu-
ated).
Fig. 34 Control via supply with relay
or
from line plus/minus, relay in the FACP
A)
B)
C)
B)
A)
from line plus/minus, relay in the ASD
from SW otuput of FACP, relay in the FACP
from SW output of FACP, relay in the ADW
from SW function of control module, power from FACP or local
Supply
Supply
Supply
Supply
Supply
Control
module
Alarm
transmitter
local
supply
local
supply
Line
Line
Line
Line
Line
OC output
OC output
FACP
FACP
FACP
FACP
FACP
PMR 81
- or +
- or +
+ or -
+ or -
Line-specific
resistances or
alarm transmitter
Line-specific
resistances or
alarm transmitter
Line-specific
resistances or
alarm transmitter
Line-specific
resistances or
alarm transmitter
ASD 532
1
2
8
13
St
Al
1
3
2
4
ASD 532
1
2
8
13
St
Al
ASD 532
1
2
8
13
St
Al
ASD 532
1
2
8
13
St
Al
ASD 532
1
2
8
13
St
Al
ASD532 Operating Manual
Summary of Contents for ASD 532
Page 1: ...ASD 532 Aspirating Smoke Detector Operating Manual ...
Page 2: ...2 88 ASD532 Operating Manual ...
Page 6: ...6 121 ASD532 Operating Manual ...
Page 7: ...Document history 7 121 Document history First edition Date 15 10 2015 ASD532 Operating Manual ...