![Incite Fire ASD 532 Operating Manual Download Page 115](http://html.mh-extra.com/html/incite-fire/asd-532/asd-532_operating-manual_2051142115.webp)
Faults
115 / 121
Continuation:
G70, RIM 1, RIM 2 faults
Code Meaning
Check:
Possible causes and remedy:
001
Fault RIM 1
Ribbon cable connection
Module
•
Ribbon cable not correctly attached or
defective
check, replace
•
Module removed and not logged off
•
Module defective
replace
016
Fault RIM 2
064
Incompatible RIM fault
Note the production version,
should be greater than 181214
•
Replace RIM
128
RIM fault, too many RIMs
Number of RIMs
•
Only 2 RIM permitted!
G71, XLM faults
Code Meaning
Check:
Possible causes and remedy:
016
Fault XLM
Ribbon cable connection
Module
•
Ribbon cable not correctly attached or
defective
check, replace
•
Module removed and not logged off
•
Module defective
replace
064
XLM fault, too many XLMs
Number of XLMs
•
Only 1 XLM permitted!
G72, SD memory card / SIM faults
Code Meaning
Check:
Possible causes and remedy:
001
SD memory card fault, missing or defec-
tive
SD memory card
•
SD memory card was removed without
logging off
•
SD memory card defective
replace
016
Fault SIM
Ribbon cable connection
Module
•
Ribbon cable not correctly attached or
defective
check, replace
•
Module removed and not logged off
•
Module defective
replace
064
SIM fault, too many SIMs
Number of SIMs
•
Only 1 SIM permitted!
G80, AMB faults
Code Meaning
Check:
Possible causes and remedy:
004
Undervoltage fault
Operating voltage < 13.9 VDC
Conductor cross-section
•
conductor cross-section too weak
must be enlarged
•
Voltage of the power supply not OK
check and correct if needed
008
Clock fault
Lithium battery
Clock setting
•
Isolation strip still present on the lithium
battery
remove
•
Clock is not set
•
Lithium battery defective
replace
032
Invalid Autolearning parameters
Autolearning configuration
AMB
•
Re-configure
Autolearning
(ASD Config)
•
AMB defective
replace
064
Parameter invalid, day/night control
Day/night control configuration
AMB
•
Re-configure day/night control
(ASD Config)
•
AMB defective
replace
ASD532