Installation
71 / 121
6.5.1
Terminal assignment Main Board AMB 32
AMB terminal
Signal
Wiring
1
+14 to +30 VDC
Main supply line from FACP
or external according to
2
0 V
3
+14 to +30 VDC
Redundant supply line from FACP
or external according to
4
0 V
5
+ power supply
Connection of
feedback signals
6
Output fault, OC (all fault events)
7
Output Alarm, OC
8
Rel. 1 (“NO”)
Fault
Connection of the line
and specifications
of the used line
9
Rel. 1 (“NC”)
10
Rel. 1 “COM”
11
Rel. 2 “NO”
Alarm
12
Rel. 2 “NC”
13
Rel. 2 “COM”
14
External reset input + (opto-isolator input)
Connection
according to
and
15
External reset input – (opto-isolator input)
16
OEM input + (opto-isolator input)
Connection similar to
(see also Sec. 2.2.8)
17
OEM input - (opto-isolator input)
18
PWR-O+
+ Power supply (+14 to 30 VDC)
Accessory bus
19
PWR-O-
– Power supply (GND)
20
Data+
RS485 connection
21
Data-
Notice
The “Fault” relay has picked up in the release state
contact Te. 10/8 closed, 10/9 open (ASD 532 under
voltage; no fault event present).
Warning
•
In some cases actuations via the OEM input may
not
comply with requirements
in accordance with EN 54-
20
and may therefore only be used after consulting with the manufacturer.
•
The OEM input is
not
line monitored.
ASD532
Operating
Manual