Commissioning
88 / 121
7.5
Download new firmware to the ASD 532
An FW upgrade can be performed in two ways:
•
From SD memory card
•
Via Ethernet port from the “ASD Config” configuration software.
7.5.1
FW upgrade from SD memory card
When upgrading the FW from the SD memory card, first the new FW must be saved to the SD memory card in the topmost di-
rectory (not in a sub-directory).
The workflow for upgrading the FW from the SD memory card is described below:
Notice
The firmware download triggers a fault relay. When upgrading the FW on the ASD 532, it is therefore absolutely
essential that
fire incident controls and remote alerting
on superordinate systems (FACP) are switched off be-
forehand.
Measure
Display
Procedure / remarks
(1)
If present, log off the SD memory card
via switch position
o
and remove.
•
See Sec. 7.3.7
(2)
Copy the FW file to be transferred to
the SD memory card and then re-insert
the SD memory card in the ASD.
•
On the SD memory card to the
topmost
level (no
sub-directory).
Important
:
only one
FW file may
be saved.
(3)
On the AMB 32, press and hold the
“
OK
” key and afterwards
briefly press
the “
HW reset
” button. Release the
“
OK
” key.
bL -
(“
Bootloader
” display)
•
Continuously lit “
Wdog
” indicator
•
“
Al
” & “
Flt
” LEDs continuously lit
•
ASD triggers fault
(4)
Transmission to the ASD 532 begins
(takes approx. 10 s)
Sd -
(displays “from SD memory
card”)
•
Transmission running
(5)
FW upgrade is completed
flashing
- - -
(approx. 4 x)
•
Fault is reset
•
ASD start phase running (LED “
Fault
” flashes
about 60 s)
•
ASD continues running with the previous installa-
tion-specific settings
•
FW upgrade is completed
Notice
Afterwards, normal data logging begins automatically on the still inserted SD memory card. If this is not wanted,
the SD memory card must be logged off and removed after the FW upgrade (via switch position
o
).
(6)
After a waiting time of at least 2 min.
from point (5) an initial reset must be
performed.
Attention
: only necessary if
expressly mentioned in the relevant
firmware description.
According to Sec. 7.3.5
•
Observe the firmware description for the loaded
FW
•
According to Sec. 7.3.5