Commissioning
93 / 121
7.7.2
Test triggerings
Notice about test triggerings
Fire incident control and remote alerting must be blocked or deactivated on the superordinate FACP.
Reset the ASD 532 between each check (preferably on the FACP, as a reset on the ASD does not reset the
FACP).
Measure
Display
Procedure / remarks
(1)
Press key
flashing
C31
or other
•
Displays the default setting or the installation-
specific switch position
(2)
Test alarm
Press the key again until the
display is on
-
I
----
in succession
A
/
b
/
C
/
E
/
F
/
I
•
Displays switch position group
I
(3)
Press key >
-
IA1
-
IA1
(possible selection here:
IA1
/
IF1
/
IP1
/
IE1
)
•
Displays test mode “Test alarm from
EasyConfig
”
(4)
Press key
3 x
flashing
IA1
(until reset)
•
ASD 532 triggers Alarm
via relay or XLM to
FACP
reset from FACP
(5)
Test fault
Press key again until display
on
-
I
----
in succession
A
/
b
/
C
/
E
/
F
/
I
•
Displays switch position group
I
(6)
Press key
IA1
•
Displays test mode “Test alarm from
EasyConfig
”
(7)
Press the key several times un-
til display on
-
IF1
-
in succession
IA1
/
IF1
•
Displays test mode “Test alarm from
EasyConfig
”
(8)
Press key
3 x
flashing
IF1
(until reset)
•
ASD 532 triggers fault
via relay or XLM to
FACP
reset from FACP
(9)
Test pre-signal
Press key again until display
on
-
I
----
in succession
A
/
b
/
C
/
E
/
F
/
I
•
Displays switch position group
I
(10)
Press key
IA1
•
Displays test mode “Test alarm from
EasyConfig
”
(11)
Press the key several times un-
til display on
-
IP1
-
in succession
IA1
/
IF1
/
IP1
•
Displays test mode “Test pre-signal from
EasyConfig
”
(12)
Press key
3 x
flashing
IP1
(until reset)
•
ASD 532 triggers pre-signal
via relay or XLM to
FACP
reset from FACP
(13)
Test alarm 2
Press key again until display
on
-
I
----
in succession
A
/
b
/
C
/
E
/
F
/
I
•
Displays switch position group
I
(14)
Press key
IA1
•
Displays test mode “Test alarm from
EasyConfig
”
(15)
Press the key several times un-
til display on
-
IE1
-
in succession
IA1
/
IF1
/
IP1
/
IE1
•
Displays test mode “Test alarm 2 from
EasyCon-
fig
”
(16)
Press key
3 x
flashing
IE1
(until reset)
•
ASD 532 triggers Alarm 2
via relay or XLM to
FACP
reset from FACP
7.8
Commissioning protocol
The ASD 532 ships with a commissioning protocol (fold-out) included in the scope of delivery. All of the measurements and
tests carried out during commissioning and maintenance are to be entered on the protocol, which is then signed.
Notice
•
When performing maintenance work or after certain other events, conclusions can be drawn concerning the
commissioning state of the ASD 532 based on the commissioning protocol. The protocol also serves as a kind
of life history of the ASD 532.
•
The commissioning protocol is to be filled out conscientiously and fully and stored in the ASD 532. If required,
a copy can be made and stored in the system dossier.
UP
UP
OK
OK
UP
OK
UP
OK
UP
OK
UP
OK
UP
OK
UP
OK
ASD532
Operating