Commissioning
81 / 121
Table B
: The following criteria apply to the entire ASD 532. Configuration changes are stored in connection with the adjust-
ments from Table A, likewise on one of the user configurable switch positions
X01
to
X03
.
Sector
•
Parameter
Default
setting
Range
Resolution /
levels
Saving after change
Autolearning
•
Autolearning
On / Off
Off
On
X01 – X03
•
Autolearning
duration
3 days
1 min to 14 days
min, h, days
X01 – X03
•
Autolearning
factor (of measured
Al
threshold)
1.5
1.1 – 10 x
X01 – X03
Day/night control & weekday control
•
Day/night control On / Off
Off
Off / clock / FACP
X01 – X03
•
Day start time
06:00
00:00 – 24:00
15 min
X01 – X03
•
Night start time
20:00
00:00 – 24:00
15 min
X01 – X03
•
Weekday control
On
Mon. to Sun.
Days
X01 – X03
General faults
•
Lithium battery / clock fault
On
On / Off
X01 – X03
Fan
•
Fan speed
Level II
Level I to III
1
X01 – X03
Deactivate sensor
•
Smoke sensor
On
On / deactivated
X01 – X03
Table C
: Independent configurations. These can be changed regardless of the switch position in the ASD 532.
Sector
•
Parameter
Default adjustment
Selection
Clock
•
Year, month, day, hour, minute
---
Minutes – year
Relay / OC output / reset key / various
•
Relay 1, 1
st
RIM 36
Pre-signal 1 smoke sensor
According to Sec. 7.2.2
•
Relay 2, 1
st
RIM 36
Pre-signal 2 smoke sensor
According to Sec. 7.2.2
•
Relay 3, 1
st
RIM 36
Pre-signal 3 smoke sensor
According to Sec. 7.2.2
•
Relay 4, 1
st
RIM 36
Smoke sensor dirt
According to Sec. 7.2.2
•
Relay 5, 1
st
RIM 36
Sampling tube blockage
According to Sec. 7.2.2
•
Relay 1, 2
nd
RIM 36
---
According to Sec. 7.2.2
•
Relay 2, 2
nd
RIM 36
---
According to Sec. 7.2.2
•
Relay 3, 2
nd
RIM 36
---
According to Sec. 7.2.2
•
Relay 4, 2
nd
RIM 36
---
According to Sec. 7.2.2
•
Relay 5, 2
nd
RIM 36
---
According to Sec. 7.2.2
•
Reset key On / Off
On
On / Off
•
Perform initial reset
---
On / Off
•
OEM input signal
Off
Off / OEM input alarm /
OEM input fault /
Day/night switching
•
Isolating the smoke sensor
Normal operation
Isolate / normal operation
ASD532
Operating
Manual