Commissioning
86 / 121
7.3.5
Initial reset
When commissioning the ASD 532, an initial reset is required. When this happens, the airflow monitoring is automatically
aligned to the connected sampling pipe.
Notice
•
In principle the initial reset should be carried out under “normal system conditions”, i.e. with any ventilation
systems, air conditioning systems, etc., running in “normal operation”.
•
If a maintenance sampling hole is provided, it must be closed with adhesive tape or the maintenance clip.
•
The initial reset must be performed with normal ventilation for equipment monitoring of ventilated objects.
•
If there is an expansion, conversion, retrofitting or repair on the sampling pipe, an initial reset is imperative.
•
An initial reset must be performed after the fan speed has been changed.
•
After an FW upgrade, an initial reset is required only if expressly mentioned in the relevant firmware descrip-
tion.
•
Before performing an initial reset after switching on the ASD 532, a
waiting time of at least 2 min
must be
observed.
Measure
Display
Procedure / remarks
(1)
Press key
flashing
C31
or other
•
Displays the default setting or the installation-
specific switch position
(2)
Press the key again until the
display is on
-
U
----
in succession
A
/
b
/
C
/
E
/
F
/
I
/
o
/
T
/
U
•
Displays the switch position group
U
(3)
Press key >
-
U01
-
U01
•
Displays initial reset on
(4)
Press the key again
flashing
U - -
(5 to max. 120 s)
•
Initial reset in progress
(5)
Wait
flashing point (watchdog indicator)
•
Initial reset completed
7.3.6
Displaying the firmware version
On the ASD 532 the switch position
F
can be used to display the version of the firmware currently loaded.
Measure
Display
Procedure / remarks
(1)
Press key
flashing
C31
or other
•
Displays the default setting or the installation-
specific switch position
(2)
Press the key again until the
display is on
-
F
----
in succession
A
/
b
/
C
/
E
/
F
•
Displays the switch position group
F
(3)
Press key
flashing after approx. 2 s,
e.g.
V01.
Pause
00.
Pause
08
•
Displays the firmware version, in this case
01.00.08
UP
UP
OK
OK
UP
UP
OK
ASD532 Operating Manual