Commissioning
7.1
General
Warning
The following points must be observed when commissioning the ASD 532:
•
The ASD 532 is to be commissioned by trained and qualified personnel only.
•
Prior to commissioning it is important to ensure that the entire sampling pipe has been laid correctly (junc-
tions, sampling holes).
•
If a maintenance sampling hole is provided as described in Sec. 4.4.4.6, it must be closed with adhesive tape
or the maintenance clip.
•
Prior to commissioning, an inspection of the mounting and installation must ensure that when the power sup-
ply is switched on there can be no damage to the ASD 532.
•
Rewiring the device may be performed only when voltage is disconnected. Exception: Logging off additional
modules XLM, RIM and SIM (see Sec. 7.3.7).
•
Before switching on, the smoke detector and any additional modules in the detector box must be fitted and
connected to the AMB 32 main board by means of the supplied flat cable. See also Sec. 6.3 and 6.4.
•
Before switching on the ASD power supply, ensure that all fire incident controls and remote alerting from the
ASD 532 are blocked or deactivated.
•
Immediately before switching on the ASD 532 for the first time, remove the isolating strip from the lithium bat-
tery (AMB 32).
•
System performance depends on the sampling pipe. Any extensions or modifications to the installation may
cause functional faults. The effects of such changes must be checked. It is very important to adhere to the
specifications in Sec. 4 (Planning). The “ASD PipeFlow” calculation software is available from the manufac-
turer.
The detector housing has to be opened for commissioning the ASD 532 (see Sec. 5.4.1).
Fig. 40 Detector housing opened for commissioning
Ethernet interface,
connection for PC
Display and
control elements
for device settings
Insulation strips
l
battery
ithium
HW
Reset button
ASD532 Operating Manual
Summary of Contents for ASD 532
Page 1: ...ASD 532 Aspirating Smoke Detector Operating Manual ...
Page 2: ...2 88 ASD532 Operating Manual ...
Page 6: ...6 121 ASD532 Operating Manual ...
Page 7: ...Document history 7 121 Document history First edition Date 15 10 2015 ASD532 Operating Manual ...