Commissioning
82 / 121
7.2.2
Relay allocation
The following criteria are freely programmable on max. 10 relays (5 units on 1
st
RIM 36, 5 units on 2
nd
RIM 36):
Smoke sensor I /
LS-Ü
I
General
Smoke sensor alarm
Fan fault
Pre-signal 1 smoke sensor
Operating voltage fault
Pre-signal 2 smoke sensor
Initial reset fault
Pre-signal 3 smoke sensor
Lithium battery / clock fault
Smoke sensor dust
Smoke sensor dirt
Smoke sensor fault
Sampling tube blockage
Pipe breakage sampling tube
Alarm 2 sampling pipe
The criteria can also be allocated using the OR function (e.g. smoke sensor dust or dirt together on one relay).
7.3
Starting up
The information on operation and display elements necessary for startup can be found in
Warning
Before the ASD 532 is switched on, all the precautions required for operation as described in Sec. 7.1 must be
fulfilled.
7.3.1
Commissioning with EasyConfig
The workflow for commissioning with
EasyConfig
is shown below (planning without “ASD PipeFlow” calculation, without
“ASD Config” configuration software). When RIM 36 additional modules are fitted, the RIM relays respond as described in Sec.
2.2.6 and 7.2.1, Table C. The default values as set out in Sec. 7.2.1 also apply to all other settings.
Fig. 43 Workflow for commissioning using EasyConfig
Point of departure: tube system(s) mounted and connected to
ASD. Smoke sensor(s) deployed in the ASD.
“
”
Switch settings defined acc. to tube system (e.g.
).
b21
Switch on supply voltage (FACP). The fan accelerates stepwise
to ist defined speed (takes about 100 s). The next process can
nevertheless be performed immediately.
Select required switch position for operation acc. to
Sec.
“
”
4.4.4.3 (e.g.
).
b21
. 7.3.5
Workflow Sec
. 7.3.4
Workflow Sec
. 7.3.3
Workflow Sec
After switching on, a
perform initial reset
minimum waiting time of 2 min
System in operation; commissioning ended
Set time and date
System is armed
Commissioning workflow
using
EasyConfig
ASD532 Operating Manual