Commissioning
80 / 121
7.2.1
Configuration options
Fig. 42 Configuration overview
Table A
: The criteria below are set separately for day/night control. Configuration changes are saved on one of the freely con-
figurable switch positions
X01
to
X03
.
Sector
•
Parameter
Default
setting
Range
Resolution /
levels
Saving after change
Alarm 2
•
Alarm 2 On / Off
Off
Off / On
X01 – X03
•
Sensitivity (always at least 20% above alarm)
1%/m
–10%/m
0.0002%/m
X01 – X03
•
Alarm 2 delay
2 s
0 s – 60 s
1 s
X01 – X03
•
Alarm 2 latching
On
On / Off
X01 – X03
•
Holding time for area switchover (
Al
2 to
Al
)
20
10 – 250
1 s
X01 – X03
Alarm (EN 54-20)
•
Alarm threshold (dependent on smoke sensor type
and response class according to EN 54-20)
C11
0.02 – 10%/m
0.1 – 10%/m
0.5 – 10%/m
0.0002%/m
X01 – X03
•
Smoke level value averaging (number)
4
1 – 10
1
X01 – X03
•
Alarm delay
2 s
0 s – 60 s
1 s
X01 – X03
•
Alarm cascading
Off
Off / On
X01 – X03
•
Alarm latching
On
On / Off
X01 – X03
Pre-signal
•
Pre-signal 1 On / Off
On
On / Off
X01 – X03
•
Pre-signal 2 On / Off
On
On / Off
X01 – X03
•
Pre-signal 3 On / Off
On
On / Off
X01 – X03
•
Pre-signal 1 (100% = alarm threshold)
30%
10 – 90%
10%
X01 – X03
•
Pre-signal 2 (100% = alarm threshold)
50%
VS 1 + 10 – 90%
10%
X01 – X03
•
Pre-signal 3 (100% = alarm threshold)
70%
VS 2 + 10 – 90%
10%
X01 – X03
•
Pre-signal delay (
VS
1 –
VS
3)
2 s
0 s – 60 s
1 s
X01 – X03
•
Pre-signal latching
Off
Off / On
X01 – X03
Smoke sensor dust/dirt
•
Smoke sensor dust On / Off
On
On / Off
X01 – X03
•
Smoke sensor dirt On / Off
On
On / Off
X01 – X03
•
Dust threshold (% of
Al
)
50%
5 – 60%
5%
X01 – X03
•
Dirt threshold (% of
Al
)
75%
65 – 90%
5%
X01 – X03
•
Dust latching
On
On / Off
X01 – X03
•
Dirt latching
On
On / Off
X01 – X03
•
Smoke sensor fault delay
30 s
0 s – 60 s
1 s
X01 – X03
Airflow monitoring
•
LS-Ü
pipe blockage On / Off
On
On / Off
X01 – X03
•
LS-Ü
pipe breakage On / Off
On
On / Off
X01 – X03
•
LS-Ü
sensitivity (applies to
A01
to
C31
)
±20%
±1 – ±70%
± 1%
X01 – X03
•
LS-Ü
value averaging (number)
20
1 – 30
1
X01 – X03
•
LS-Ü
delay (applies to
A01
to
C31
)
300 s
2 min – 60 min
10 s / 1 min
X01 – X03
Notice
Stored in switch positions
W01
to
W44
are increased values that are not tested for EN compliance (see Sec.
no
Change of the
default setting
yes
no
Change of
default setting
Save on switch
setting level
,
or
X01 X02
X03
Save on device level
(independent of
switch setting
A, B, C, W or X)
Operation of the
ASD 532
in switch setting
,
or
X01 X02
X03
Operation of the ASD 532
in switch setting
-
or
A11 C31
W01 - W44
Operation of the ASD 532
in switch setting
-
or
-
A11 C31, W01 - W44
X01 X03
Criteria:
Default
setting
Change:
Save:
Operation:
- Autolearning
- Day/night control
- General fault
- Fan
General
- Initial reset
- Date/time
- Relay assignment
- Reset key
Independent
- Smoke sensor
- LS-Ü
- Smoke sensor
- LS-Ü
D
a
y
N
ig
h
t
Rauchsensor / LS-Ü
Table A:
Table B:
Table C:
yes