Installation
68 / 121
6
Installation
6.1
Regulations
Danger
The electrical installation is to be carried out in accordance with the applicable country-specific regulations, stan-
dards and guidelines. Likewise, the local provisions must also be observed.
Notice
Besides country-specific regulations and guidelines, the specifications concerning the requirements for installa-
tion cables and conductor cross-sections as described in Sec. 4.8 must be observed and implemented.
6.2
Cable entry
Danger
Make sure the power is disconnected for all connection and wiring work on the ASD 532.
There are two M20 cable screw unions in the detector housing for feeding in the electrical installation. If needed, an additional
two cable screw unions (1 x M20, 1 x M25) can be fitted in two reserve holes (blind plugs).
The cable screw unions are suitable for cables with external diameters ranging between 5 and 12 mm (M20) or 9 and 18 mm
(M25).
Notice
The device ships with the cable screw unions sealed with a dust-protection insert; remove the inserts before feed-
ing in the cables. The dust-protection inserts merely prevent the ingress of any dust and/or dirt during the mount-
ing of the device and do not provide any mechanical protection. Any cable screw unions that are not in use must
be replaced with blind plugs (mounting set) to maintain the IP 54 protection class.