Operation
104 / 121
8.5.6
Operation and display on the SIM 35
Fig. 47 SIM 35 operation and display
The functions of the rotary switches, jumpers, buttons and LEDs are shown in the following table.
The network address is set in hexadecimal code using the two rotary switches (S1 and S2). The bus termination is defined
with the
TERM
jumper. This must be performed on
both sides of the network
(beginning and end). The
BOOT-MODE
jumper
is used only in production. The
RESET
button initiates a HW reset on the SIM 35. The four LEDs on the SIM 35 indicate the
state of the ASD network. Please refer to Sec. 11.4 for more information about the ASD network.
Rotary switch S1 / S2
Network address
Jumper
TERM
Bus termination (position “C” = active)
Position
O
SIM 35 is
not
first or last module
Position
C
SIM 35 is
first
or
last
module
Jumper
BOOT-MODE
FW upgrade (production)
Position
R
Normal position
Position
P
Local FW upgrade on the SIM 35
Button
RESET
SIM reset
Press
Triggers a HW reset of the SIM 35
LED PG (green)
State of voltage supply
Continuously lit
Power supply from AMB 32 OK
LED PGI (green)
State of internal voltage supply
Continuously lit
Internal voltage supply OK
LED COM (green)
State of communication
Flashes
Communication in progress, “ASD Config” is ac-
tive
LED ERR (yellow)
State SIM / fault
Flashes
Address is in invalid range
Continuously lit
SIM has fault
1
2
3
4
5
6
RESET
button
LED
PG
LED
COM
LED
ERR
LED
PGI
TERM
jumper
BOOT-MODE
jumper
S1 / S2 rotary switches
for network address
AMB
ASD532
Operating
Manual