General
13 / 121
1
General
1.1
Purpose
The ASD 532 aspirating smoke detector has the task of continuously taking air samples via a sampling pipe tube network from
a monitored area and feeding the samples to a smoke sensor. Thanks to this detection method and the product’s excellent
properties under severe ambient conditions, the ASD 532 aspirating smoke detector is used wherever problems are to be ex-
pected owing to poorly accessible monitored areas or latent disturbance variables during operation such that optimal protec-
tion can no longer be guaranteed with conventional point detectors.
The SSD 532 smoke sensor is used in the ASD 532. It is available in the three following versions and sensitivity ranges:
•
SSD 532-1
Alarm sensitivity range 0.5%/m to 10%/m
•
SSD 532-2
Alarm sensitivity range 0.1 %/m to 10%/m
•
SSD 532-3
Alarm sensitivity range 0.02%/m to 10%/m.
The ASD 532 aspirating smoke detector has two slots for additional modules. The following modules can be fitted:
•
XLM 35
eXtended Line Module
•
RIM 36
Relay Interface Module with 5 relays;
•
SIM 35
Serial Interface Module.
With the installation of a eXtended Line Module
XLM 35
the ASD 532 aspirating smoke detector can be ideally connected to
the fire alarm systems SecuriFire (SecuriLine eXtended) and Integral (X-Line) via the addressable loop. Control operations and
changes to the ASD device configuration can be carried out directly from the FACP (in preparation). For this purpose the
FACP user software “SecuriFire Studio” and “
Integral Application Center
” are used to start the “ASD Config” configuration
software for access to the ASDs; the configuration software is then used to make changes to the ASD 532.
A further installation option is the
RIM 36
relay interface module. This module enables the availability of all three pre-signal
levels as well as the states “smoke sensor dirty” and “
LS-Ü
pipe blockage” as relay contacts. The relays are also freely pro-
grammable via the “ASD Config” configuration software.
The
SIM 35
Serial Interface Module is for networking multiple ASD 532 aspirating smoke detectors via RS485 bus. Using the
“ASD Config” configuration software, all ASD 532 units present in the network can be visualised and operated from a PC. The
master module in the ASD network is the SMM 535, by means of which a PC is connected.
Notice
The normative alarm transmission of the ASD 532 to the superordinate centre does not take place via the ASD
network. For that purpose the “Alarm” / “Fault” relays in the ASD or the SecuriFire / Integral addressable loop are
to be used from the XLM 35.
The present technical description contains all information essential for trouble-free operation. For obvious reasons only those
details specific to individual countries and companies or special applications can be discussed if they are of general interest.
ASD532
Operating
Manual
Summary of Contents for ASD 532
Page 1: ...ASD 532 Aspirating Smoke Detector Operating Manual ...
Page 2: ...2 88 ASD532 Operating Manual ...
Page 6: ...6 121 ASD532 Operating Manual ...
Page 7: ...Document history 7 121 Document history First edition Date 15 10 2015 ASD532 Operating Manual ...