Technical data
120 / 121
13
Technical data
Type
ASD 532
Supply voltage range
14 to 30
VDC
Max. power consumption, measured in
typical
Fan speed level III and at
14 VDC
24 VDC
ASD 532-1
Quiescent/fault
approx. 170
approx. 100
mA
Alarm
approx. 200
approx. 115
mA
additionally with 1x RIM 36
approx. 30
approx. 15
mA
additionally with 2x RIM 36
approx. 60
approx. 30
mA
additionally with XLM 35
approx. 15
approx. 5
mA
additionally with SIM 35
approx. 15
approx. 5
mA
SMM 535 (not from ASD but rather from PC via USB connection)
max. 100
mA
Switch-on current peak
(caused by EMC protection elements on the ASD supply input)
approx. 5
A
for max. 1
ms
Sampling pipe length
see Sec. 4.2.1
Sampling pipe diam., typical (inner/outer)
Ø 20 / 25
mm
Max. number of sampling holes
see Sec. 4.2.1
Sampling hole diameter
Ø 2 / 2.5 / 3 / 3.5 / 4 / 4.5 / 5 / 5.5 / 6 / 6.5 / 7
mm
Response range
EN 54-20, class A, B, C
Protection type compliant with IEC 529 / EN 60529 (1991)
54
IP
Ambient conditions compliant with IEC 721-3-3 / EN 60721-3-3 (1995)
3K5 / 3Z1
class
Extended ambient conditions:
•
Detector housing temperature range
–20 – +60
°C
•
Sampling pipe temperature range
–20 – +60
°C
•
Max. permissible temperature fluctuation in detector housing and sampling pipe operation
20
°C
•
Max. permissible storage temperature for detector housing (without condensation)
–30 – +70
°C
•
Ambient pressure difference between detector housing and sampling pipe (sampling holes)
must be identical
•
Humidity ambient condition for detector housing (transient without condensation)
95
% rel. h
•
Humidity ambient condition (continuous)
70
% rel. h
Max. loading capacity, relay contact
50
VDC
1
A
30
W
Max. loading capacity per OC output (dielectric strength 30 VDC)
100
mA
Plug-in terminals
2.5
mm²
Cable entry for cable Ø
Ø 5 – 12 (M20) / Ø 9 – 18 (M25)
mm
Noise level
min. (if fan speed level I)
24.5
dB (A)
max. (at fan speed level III)
39.5
dB (A)
Housing
material
ABS blend, UL 94-V0
colour
grey 280 70 05 / anthracite violet 300 20 05
RAL
Approvals
EN 54-20
Dimensions
ASD 532-1 (W x H x D, without/with packaging)
195 x 333 x 140 / 215 x 355 x 160
mm
SSD 532-x (W x H x D, with packaging)
128 x 130 x 175
mm
Weight
ASD 532-1 (without/with packaging)
1,700/1,950
g
SSD 532-x (with packaging)
335
g
Notice
Power consumption at maximum permitted voltage drop in the electrical installation (decisive value for calcu-
lating the conductor cross-section).
May cause the protective circuit to trigger immediately in the case of power supplies with overload protective
circuits (primarily in devices with no emergency power supply and output current of < 1.5 A).
Lower or higher temperature ranges are also possible subject to consultation with the manufacturer. The
manufacturer must be consulted if the device is used in the condensation range.
ASD532
Operating
Manual
Summary of Contents for ASD 532
Page 1: ...ASD 532 Aspirating Smoke Detector Operating Manual ...
Page 2: ...2 88 ASD532 Operating Manual ...
Page 6: ...6 121 ASD532 Operating Manual ...
Page 7: ...Document history 7 121 Document history First edition Date 15 10 2015 ASD532 Operating Manual ...