Options
118 / 121
11.4.2
ASD networking via Ethernet interface from AMB 32
Via the Ethernet interface directly from the ASD 532 (AMB 32) several ASDs can be networked amongst themselves. An ASD
network can have up to 250 participants. This network can be considered an independent network. Integration of the ASDs
into an existing IT network or via the internet (remote access) is not possible. The general rules and Ethernet technology apply
to constellation and design. The example below shows a possible variant of an ASD network via Ethernet interface.
Fig. 52 Design of an Ethernet ASD network
Important notice about commissioning:
•
The line length between the participants as shown
in
(switch – ASD / switch – PC) is a maxi-
mum of 100 m.
•
If longer lines are required, use fibre optics technol-
ogy.
•
Each ASD requires its own permanently program-
med IP address.
•
This IP address is not automatically assigned.
•
For this reason initial commissioning must be per-
formed on each ASD directly on the device for as-
signing the IP address (with “ASD Config”).
•
The address range should be within
169.254.xxx.xxx.
ASD
ASD
ASD
ASD
. . .
PC
Switch
ASD532
Operating
Manual