Operation
105 / 121
8.5.7
Operation and display on the SMM 535
Fig. 48 SMM 535 operation and display
The functions of the jumpers and LEDs are shown in the following table.
The bus termination is defined with the
TERM
jumper. This must be performed on
both sides of the network
(beginning and
end). The three LEDs on the SMM 535 indicate the state of the ASD network. Two of these are fibre optic cables on the out-
side of the housing (
FAULT
LED is not fitted, optional).
Jumper
TERM
Bus termination (position “C” = active)
Position
O
SMM 535 is
not
first or last module
Position
C
SMM 535 is
first
or
last
module
POWER (PG) (green)
State of voltage supply
Continuously lit
Power supply from PC (USB) OK
COM (USB) (green)
State of communication
Flashes
Communication in progress, “ASD Config” is active
LED PGI (green)
State of internal voltage supply
Continuously lit
Internal voltage supply OK
No network address has to be assigned to the SMM 535.
8.6
Operation from SecuriFire / Integral with XLM 35
When connecting to the SecuriFire or Integral FACP via an
XLM 35
, control operations and changes can be made to the ASD
device configuration directly from the FACP. For this purpose the FACP user software “SecuriFire Studio” and “
Integral Appli-
cation Center
” are used to start the “ASD Config” configuration software for access to the ASDs; operation is then carried out
on the ASD 532.
G
N
D
D
+
D
-
Network
connection
USB
port
Displays:
-
-
-
FAULT (ERR)
COM (USB)
POWER (PG)
LED
PGI
TERM
jumper
ASD532
Operating
Manual