Commissioning
79 / 121
7.2
Programming
The ASD 532 has several switch positions that are configured with permanently assigned parameters:
•
normative system limits according to EN 54-20, Class A to C, switch positions
A11
to
C31
;
•
Non-normative system limits, switch settings
W01
to
W44
;
•
Configurable switch positions for saving the settings after using “ASD PipeFlow” and/or changing the device configuration
using the configuration software “ASD Config” or SecuriFire or Integral-FACP (XLM 35),
X01
to
X03
.
A detailed description of all switch positions is in Sec. 8.3.
If the ASD 532 is operated with
EasyConfig
, i.e. within the preset system limits according to the tables in Sec. 4.4.4.3 and
4.4.4.4, then only switch settings
A11
to
C31
and
W01
to
W44
are to be selected; it is not necessary to use the “ASD Config”
configuration software.
In systems where the sampling pipe planning was performed with the “ASD PipeFlow” calculation software, the response sen-
sitivities of the smoke sensors calculated by “ASD PipeFlow” have to be programmed on the ASD 532 with “ASD Config”. The
data is saved on the ASD 532 under one of the freely configurable switch positions
X01
to
X03
. The ASD 532 is then operated
on the switch positions
X01
to
X03
.
The device ships with default values already stored under switch positions
X01
to
X03
. Specifically:
•
position
X01
with position
A11
;
•
position
X02
with position
b11
;
•
position
X03
with position
C11
;
The following parameters can be modified using the “ASD Config” configuration software (see Sec. 7.2.1):
•
Smoke sensor alarm thresholds;
•
Trigger thresholds for dust and dirt (individually);
•
Trigger thresholds for pre-signals 1, 2 and 3 (individually);
•
Delay times for dust/dirt, pre-signal, alarm and fault (individually);
•
Sensitivity and delay time of the airflow monitoring;
•
Deactivate latching for dust/dirt, pre-signal, alarm and fault (individually);
•
Deactivate criteria (pre-signals, dust/dirt, faults);
•
Fan speed
•
Date/time
•
Autolearning (On/Off, duration);
•
Day/night operation
•
Relay assignment (RIM 36)
Warning
The parameters are configured ex factory with default states and values so that the triggering properties comply
with EN 54-20. Changing the parameters may result in non-compliance with EN 54-20. Adjustments or modifica-
tions to the ASD 532 using “ASD Config” may be carried out only by the manufacturer or by persons under the
supervision of and trained by the manufacturer.
Fig. 41 Control and indicator elements on the AMB 32
(16)
(16)
(8)
AMB 32
Option3
Option1
Option2
BAT
R
e
s
e
t
OK
HW-Reset
SENS
SSD
Vent
21 20
19
18
17
16 15
14
13 12
11 10
9
8
7
6
5
4
3
2
1
Ethernet
UP
CardOK
Com
Wdog
Pwr
Al
Flt
Det.
dusty
dirty
1
2
3
4
5
6
7
8
9
10
LED1
LED2
LED3
LED4
HW-Reset
button
Watchdog
display
SD Card
communication display
Ethernet interface
Display elements
Selection key “
”
UP
Confirmation key “
”
OK
ASD532
Operating
Manual
Summary of Contents for ASD 532
Page 1: ...ASD 532 Aspirating Smoke Detector Operating Manual ...
Page 2: ...2 88 ASD532 Operating Manual ...
Page 6: ...6 121 ASD532 Operating Manual ...
Page 7: ...Document history 7 121 Document history First edition Date 15 10 2015 ASD532 Operating Manual ...