Procedure
Step 1 (Optional) Remove the LCD from the front door of the smart cooling product.
NO TE
● The LCD cables have been preinstalled on the smart cooling product. You only need to
remove the cable connector from the LCD.
● Reserve the LCD and cables for installing the aisle door.
Step 2 Remove the perforated front door delivered with the smart cooling product.
Step 3 Remove the beam from the cabinet.
Step 4 Install the glass aisle door.
1. Align the glass aisle door with the holes in the cabinet. Use four M5x10
tapping screws to secure it at the front holes on the top of the cabinet. The
following figure shows the installation positions.
Figure 3-27 Securing holes on the cabinet top
2. Use three M5x10 tapping screws to secure the glass aisle door to the bottom
of the cabinet.