After an alarm is cleared, prepare a report to record the alarm handling process.
NO TE
Common alarm references are as follows:
● Data center infrastructure alarm reference in the online help of the management system
● Alarm references in documents delivered with components
● Alarm reference in this document
● Alarm reference obtained from Huawei technical support
It is recommended that the alarm handling report consists of information about the alarm
occurrence time, location, symptom, fault locating process, alarm handling process, and
alarm prevention solutions.
6.3 Parts Replacement
6.3.1 ECC800-Pro Common Operations
6.3.1.1 Preparations and Login
Prerequisites
●
Supported operating system: Windows 7 and later versions
●
Recommended screen resolution: 1366 x 768 or higher
●
Browser: Chrome, Firefox, Internet Explorer 11 or later
Procedure
Step 1 Connect the PC network port and the WAN1 port (protected by a security
mechanism) on the ECC800-Pro using a network cable.
Table 6-13 Default IP addresses for the WAN and LAN ports on the ECC800-Pro
Port
Default IP Address
WAN1
192.168.8.10
WAN2
192.168.0.10
192.168.248.10 (FusionModule800)
LAN1 and LAN2
192.168.248.10
FusionModule2000-S Smart Modular Data Center
User Manual
6 Operation and Maintenance
Issue 03 (2021-07-15)
Copyright © Huawei Technologies Co., Ltd.
240