Table 6-10 Semiannual maintenance for the management system
Maintenanc
e Item
Method
Expected Result
Troubleshooting
Availability
of the smart
ETH gateway
On the ECC800-
Pro WebUI,
choose
Monitoring >
System > Smart
ETH Gateway
Group > Smart
ETH Gateway.
On the Running
Info page, view
the
communication
status, PoE port
connection, and
power supply
status.
The connection
status and power
supply status of the
PoE port on the
smart ETH gateway
can be queried on
the ECC800-Pro
WebUI.
If the display is
abnormal, check
whether the
communications
cable is loose or
disconnected. If so,
reconnect the cable.
If not, replace the
smart ETH gateway.
Availability
of the
cabinet
electronic
lock
Observe the
cabinet electronic
lock indicator and
check the lock
function by
swiping a card.
After the card is
swiped, the green
indicator is on and
the door lock is
open.
If the door is
abnormal, replace the
access card. If the
door can be opened
after the access card
is replaced, record
the access card again.
If the door still
cannot be opened,
check the cable
connection and
power supply of the
cabinet electronic
lock. If the cable
connection and
power supply are
abnormal, replace the
cabinet electronic
lock.