Table 5-7 Initial passwords
System User
Initial Password
admin (system administrator)
000001
operator (common user)
000001
Step 6 Perform quick settings.
Table 5-8 Settings Wizard
Item
Parameter
Setting
Language
-
Set as required.
Data and
Time
Date format
Set as required.
YYYY-MM-DD
Actual date
Time zone
Actual time zone
Time (H:M:S)
Actual time
Network
Param.
IP address assign
DHCP Automatic
System
Param.
Rated frequency
Set as required.
Rated line voltage
Set as required.
Step 7 Check whether there is any alarm on the monitoring screen. If there is, clear it.
Step 8 Switch on the input circuit breakers for smart cooling products in the integrated
PDF.
NO TE
After the input switch in the PDF is turned on, the MDU will report a Branch Disconnected
alarm, which is a normal phenomenon.
Step 9 Switch on the output circuit breakers for smart cooling products in the integrated
PDF to power on the smart cooling products.
Step 10 (Optional) Switch on the lighting output circuit breaker in the integrated PDF and
check whether the PWR indicator on the fusion module actuator lights up. Press
the lighting button to power on the lights.
Step 11 Switch on the IT input circuit breakers in the integrated PDF.
Step 12 Switch on the network cabinet output circuit breaker in the integrated PDF and
switch on the rPDU input circuit breaker in the network cabinet to power on the
network cabinet.
Step 13 Switch on the IT output circuit breakers in the integrated PDF one by one and
switch on the rPDU input circuit breaker in the IT cabinets to power on the IT
cabinets.
FusionModule2000-S Smart Modular Data Center
User Manual
5 Power-On Commissioning
Issue 03 (2021-07-15)
Copyright © Huawei Technologies Co., Ltd.
133