Figure 3-109 Cable connections to T/H sensors and temperature sensors
Figure 3-110 Cable connections to T/H sensors
(1) ECC800-Pro
(2) T/H sensor 2
(3) T/H sensor 1
(4) T/H sensor 3
(5) T/H sensor 4
(6) Temperature sensor
NO TE
T/H sensors are connected in series.
----End
3.10.13 (Optional) Installing T/H Sensors (33010516)
Context
In the hot aisle containment scenario, you do not need to install a new T/H sensor.
Attach the T/H sensors delivered with a smart cooling product to the front door
post of the adjacent IT cabinet.
Procedure
Step 1 Attach the bottom of the T/H sensor to the 33 U position on the IT cabinet door
frame.