Figure 3-45 Layout diagram
(1) General input unit
(2) Power distribution unit
(3) Aisle containment
Figure 3-46 Cabling diagram
3.9.3.2 Layout and Cable Routing Principles: Single-Row Aisle Containment
(N+1 Scenario)
●
The number of power distribution units allocated to each row of cabinets
must be an even number.
●
If the power density per cabinet is less than or equal to 10 kW, single-phase
power distribution units are used and each power distribution unit supports a
maximum of six IT cabinets. One power distribution unit provides six power
outputs to route A, and the other power distribution unit provides six power
outputs to route B for the corresponding cabinets.
●
If the power density per cabinet is greater than 10 kW, three-phase power
distribution units are used and each power distribution unit supports a
maximum of two IT cabinets. One power distribution unit provides two power
outputs to route A, and the other power distribution unit provides two power
outputs to route B for the corresponding cabinets.
●
The figures use single-phase power distribution units as an example.