If the connection is abnormal, check whether the device is properly
connected to the ECC800-Pro, whether the device and the ECC800-Pro are
running properly, and whether the parameter settings are consistent with
the device parameters.
5. Repeat
to connect other cabinet electronic clasp locks.
6. Click Unhide All Advanced Signals, then click Power Supply Parameters.
Ensure that I power supply enable(AIDI_2/COM1/AIDI_4/COM3) and II
power supply enable(AIDI_3/COM2/AIDI_5) are Enable.
Step 5 Commission the cabinet electronic clasp locks.
Table 5-30 Function commissioning
Function Path
Operation
View
cabinet
electroni
c clasp
lock
informati
on
Choose
Monitoring >
Cabinet > IT
Cabinet101 >
E-LOCK1a.
Click the
Running Info
tab.
View the running information
about cabinet electronic clasp
lock 1 on the WebUI.
Change
a cabinet
electroni
c clasp
lock
name
Click the
Running
Parameters tab.
Change the cabinet electronic
clasp lock name.
Remotely
open a
cabinet
electroni
c clasp
lock
Choose
Monitoring >
Cabinet > IT
Cabinet101a.
Click the
Controls tab.
Select Open front door or Open
back door from the Cabinet
door control drop-down list box,
and click Submit to remotely
open the door.
Open
cabinet
electroni
c clasp
locks in
batches
Choose Monitoring > Cabinet,
and click the Controls tab.
Select Open front door, Open
back door, or Open all doors
from the Open the door drop-
down list box, select the setting,
and click Submit. The cabinet
electronic clasp locks unlock the
doors in batches based on the
signal value.
a: Cabinet electronic clasp lock 1 of IT cabinet 101 is used as an example.
NO TICE
Only IT cabinets support remote door opening and closing.