NO TICE
● The BCB off alarm (the red indicator is steady on) is displayed on the SmartLi
LCD. No action is required. After the battery circuit breaker is switched on, the
alarm is automatically cleared.
● The green indicator blinks intermittently. After 1 minute, the BCU starts. The
green indicator blinks at super short intervals and the red indicator is steady
on.
● If multiple SmartLi cabinets are combined, press and hold the POWER ON/OFF
button on the BCU of the master cabinet for more than 2s to power on the
master cabinet. Then, power on slave cabinets one by one in the same way.
Step 3 Set the language, time, date, network parameters, and system parameters on the
Settings Wizard screen of the SmartLi.
Figure 5-5 Settings Wizard
FusionModule2000-S Smart Modular Data Center
User Manual
5 Power-On Commissioning
Issue 03 (2021-07-15)
Copyright © Huawei Technologies Co., Ltd.
129