Figure 3-47 Layout diagram
(1) General input unit
(2) Power distribution unit
(3) Aisle containment
Figure 3-48 Cabling diagram
3.9.3.3 Installing an NMW
Prerequisites
Install the NMW from the first IT cabinet at the end of a row.
Procedure
Step 1 After determining the position for installing the first support, use a laser locator to
locate the positions of other supports. Ensure that they are arranged neatly.
Step 2 Secure the supports.
NO TICE
● The following procedure describes how to install a low support that applies to
the cabinet front door scenario.
● If there are bolts in the holes for securing the supports, remove the bolts and
then secure the supports.
● If the cabinet edges are uneven, secure the supports to the higher cabinet edge
and use a level to ensure that the adjacent supports are flush in the front and
rear directions.
FusionModule2000-S Smart Modular Data Center
User Manual
3 Hardware Installation
Issue 03 (2021-07-15)
Copyright © Huawei Technologies Co., Ltd.
60