6. Check whether the round connector is securely installed. You can slightly pull
the connector to check whether it is loose. If it is loose, install it again.
NO TICE
● When a cable terminal is connected in place, you will hear a click.
● You need to install a ring buckle to fasten the cable terminal.
● If not prefabricated, the cables from the power distribution unit to the cabinet
rPDU need to be prepared onsite. For details, see the appendix
Table 4-2 Load cable silk screen
Output Connector
Single-Phase Power
Distribution Unit
Three-Phase Power
Distribution Unit
XT1
QF1
QF1
QF2
XT2
QF3
QF2
QF4
XT3
QF5
-
QF6
FusionModule2000-S Smart Modular Data Center
User Manual
4 System Cabling
Issue 03 (2021-07-15)
Copyright © Huawei Technologies Co., Ltd.
110