n
Input Impedance : >1 megohm for volts and 250 ohms for mA
inputs
n
Galvanic Input Isolation:
l
400 VDC point to point, solid state switching;
l
1K VDC to logic.
n
Noise Rejection:
l
Series Mode >31dB
l
Common Mode >90dB at 120VAC
n
Over-range limit: +/- 10% for linear ranges
n
Accuracy:
Factory configured accuracy = ± 0.1 % of range with below
Reference condition:
Temperature = 25 °C ± 3 °C (77 °F ± 5 °F)
Humidity = 45 % to 55 % RH non-condensing
Line voltage = Nominal ± 1 %
Source resistance = 0 ohm
Series mode and common mode = 0 V
Frequency = Nominal ± 1 %
n
Temp. Effect on Accuracy: ±0.01% of full scale per degree Celsius
maximum
n
A/D Converter: One per module
n
A/D resolution: ±15Bits
n
Update rate: 100ms (Analog to Digital Converter per module)
n
Long term Stability: 0.1% per year
n
Channel Configuration Data : Stored in non-volatile memory.
n
Power supply loading: 5V ; 75mA max 24V ; 50mA max
Digital Input Module-Contact Type (16 Channel)
16 channel Contact Type:
n
Inputs per module: 16 (single-ended)
n
Voltage supplied: 15 V DC nominal
n
Maximum Contact Resistance: 1000 ohms
98
Summary of Contents for ControlEdge 900 platform
Page 6: ...6 Contents ...
Page 12: ...12 Chapter 1 About this guide ...
Page 52: ...52 ...
Page 57: ...57 One Slot Rack 1 CPM 1 EPM 1 P S 1 RM ...
Page 59: ...59 One Slot Rack ...
Page 62: ...Figure 5 7 Rack dimensions with redundant power supply 62 ...
Page 75: ...75 c Insert the Ethernet cables and mount the security cover for the EMP ...
Page 76: ...d Optional mount a wire security seal The user should get a wire security seal themselves 76 ...
Page 124: ...Figure 5 31 Universal Analog Input Wiring Figure 5 32 Examples of RTD Input Wiring 124 ...
Page 137: ...137 Figure 5 47 Pulse Outing Wiring Figure 5 48 Frequency Wiring ...
Page 144: ...Figure 5 57 16 point High Level Analog Input Wiring 144 ...
Page 147: ...147 Figure 5 60 AC DC Isolated Input Module Wiring ...
Page 148: ...148 ...
Page 168: ...168 ...
Page 178: ...178 Chapter 8 Diagnostics and Troubleshooting ...
Page 222: ...Appendix A Installing RTP 222 ...
Page 227: ...Appendix A Installing RTP Relay Output RTP Internal schematic 227 ...