Item
Description
Short Circuit Current
24.5 mA +/- 0.5 mA
Open Wire Current
<1mA
Input Impedance
Typically 250 ohm
A-D conversion
16 bit
Accuracy
0.1% of full scale (23.5 ± 2°C)
0.17% of full scale (-0 to 60°C)
Input filter
First-order low-pass 100Hz
The following items are not directly supported by UIO AIs:
n
Voltage inputs (1-5 or mv)
n
Thermocouples
n
RTDs
n
NAMUR devices
n
Devices that supply current, which is not first supplied by the
external 24V to the device. For example, a device that creates
current (even if referenced to Honeywell ground).
Standard 2-wire transmitter with UIO
Figure 5-23: Standard 2-wire transmitter with UIO (Loop Powered)
112
Summary of Contents for ControlEdge 900 platform
Page 6: ...6 Contents ...
Page 12: ...12 Chapter 1 About this guide ...
Page 52: ...52 ...
Page 57: ...57 One Slot Rack 1 CPM 1 EPM 1 P S 1 RM ...
Page 59: ...59 One Slot Rack ...
Page 62: ...Figure 5 7 Rack dimensions with redundant power supply 62 ...
Page 75: ...75 c Insert the Ethernet cables and mount the security cover for the EMP ...
Page 76: ...d Optional mount a wire security seal The user should get a wire security seal themselves 76 ...
Page 124: ...Figure 5 31 Universal Analog Input Wiring Figure 5 32 Examples of RTD Input Wiring 124 ...
Page 137: ...137 Figure 5 47 Pulse Outing Wiring Figure 5 48 Frequency Wiring ...
Page 144: ...Figure 5 57 16 point High Level Analog Input Wiring 144 ...
Page 147: ...147 Figure 5 60 AC DC Isolated Input Module Wiring ...
Page 148: ...148 ...
Page 168: ...168 ...
Page 178: ...178 Chapter 8 Diagnostics and Troubleshooting ...
Page 222: ...Appendix A Installing RTP 222 ...
Page 227: ...Appendix A Installing RTP Relay Output RTP Internal schematic 227 ...