Hardware configuration of I/O module type
n
UOC I/O Expansion Network Topology
UOC has four Ethernet ports. Port 3 and 4 are used to connect to I/O
network, used for I/O. Table below shows UOC supported these
network topologies.
Topology Type
Description
Switch Types
Topology 1
HSR ring to 900 I/O.
None
Topology 2
Non-redundant star to 900 I/O
Generic
Topology 3
Redundant star (via PRP) to 900 I/O
Generic
Topology 4
DLR direct connection to 900 I/O and
EIP devices
None
Topology 5
DLR ETAP connections 900 I/O and
EIP devices.
ETAPs for EPMs or non-
DLR devices
Topology 6
Non-redundant star to 900 I/O and
EIP devices
Generic and stratix
Uplink and downlink subnets must be unique. The Downlink subnet
mask must be limited to the number of addresses expected in that
subnet.
For example, if a max of 64 addresses is expected, you could use a
mask of 255.255.255.192.
HSR Ring to 900 I/O
When connecting to ControlEdge 900 I/O only, a redundant ring
topology may be used. The ring type is HSR (High Availability
Seamless Redundancy). In this topology no third party redundancy
boxes are required. The UOC CPM connects directly, using its two
downlink Ethernet ports. Similarly, EPM modules connect directly
using their two Ethernet ports. When a UOC downlink is constructed
in this fashion, it is not possible to connect third party I/O, Devices or
PLCs. Only 900 I/O racks may be connected.
When connecting CPMs and EPMs into an I/O network ring, the
numbered ports must be connected so that odd numbered ports
always connect to even numbered ports. This is shown in the
34
Summary of Contents for ControlEdge 900 platform
Page 6: ...6 Contents ...
Page 12: ...12 Chapter 1 About this guide ...
Page 52: ...52 ...
Page 57: ...57 One Slot Rack 1 CPM 1 EPM 1 P S 1 RM ...
Page 59: ...59 One Slot Rack ...
Page 62: ...Figure 5 7 Rack dimensions with redundant power supply 62 ...
Page 75: ...75 c Insert the Ethernet cables and mount the security cover for the EMP ...
Page 76: ...d Optional mount a wire security seal The user should get a wire security seal themselves 76 ...
Page 124: ...Figure 5 31 Universal Analog Input Wiring Figure 5 32 Examples of RTD Input Wiring 124 ...
Page 137: ...137 Figure 5 47 Pulse Outing Wiring Figure 5 48 Frequency Wiring ...
Page 144: ...Figure 5 57 16 point High Level Analog Input Wiring 144 ...
Page 147: ...147 Figure 5 60 AC DC Isolated Input Module Wiring ...
Page 148: ...148 ...
Page 168: ...168 ...
Page 178: ...178 Chapter 8 Diagnostics and Troubleshooting ...
Page 222: ...Appendix A Installing RTP 222 ...
Page 227: ...Appendix A Installing RTP Relay Output RTP Internal schematic 227 ...