121
The field wire must be connected with one of the following OUT pins
(together with the branch). One of the OUT pins can be used for
connecting the return field wire.
n
Two DO channels with a two pin branch
n
Three DO channels with a three pin branch
Universal Analog Input Module (UAI) Wiring
The Universal Analog Input Module has eight inputs, which can
include any combination of the following input types: RTD, TC, Ohms,
Millivolt, Volt, or Milliamp. Figure shows wiring examples of each of
the analog input types. An example of wiring for eight TC inputs is
given in
Analog Input Wiring - Eight TCs
section.
Specifications for this module, see
section.
ATTENTION:
To indicate sensor failure the Analog Input software will output
a warning if thermocouple resistance > 80 ohms. Use
appropriate gauge wiring to prevent inaccurate failure
warnings.
Table 5-20: Typical Thermocouple resistance in Ohms per Double Foot @ 68 degrees F
AWG
No.
Diameter
inches
Type
K
Type
J
Type T
Type
E
Type S
Pt/
PT110
Type R
Pt/
PT113
Type
W5/
W26
Type
W/
W26
10
0.102
0.058
0.034
0.029
0.069
0.018
0.018
0.023
0.020
12
0.081
0.091
0.054
0.046
0.109
0.028
0.029
0.037
0.031
14
0.064
0.146
0.087
0.074
0.175
0.045
0.047
0.058
0.049
16
0.051
0.230
0.137
0.117
0.276
0.071
0.073
0.092
0.078
18
0.040
0.374
0.222
0.190
0.448
0.116
0.119
0.148
0.126
20
0.032
0.586
0.357
0.298
0.707
0.185
0.190
0.235
0.200
24
0.0201
1.490
0.878
0.7526
1.78
0.464
0.478
0.594
0.560
26
0.0159
2.381
1.405
1.204
2.836
0.740
0.760
0.945
0.803
Summary of Contents for ControlEdge 900 platform
Page 6: ...6 Contents ...
Page 12: ...12 Chapter 1 About this guide ...
Page 52: ...52 ...
Page 57: ...57 One Slot Rack 1 CPM 1 EPM 1 P S 1 RM ...
Page 59: ...59 One Slot Rack ...
Page 62: ...Figure 5 7 Rack dimensions with redundant power supply 62 ...
Page 75: ...75 c Insert the Ethernet cables and mount the security cover for the EMP ...
Page 76: ...d Optional mount a wire security seal The user should get a wire security seal themselves 76 ...
Page 124: ...Figure 5 31 Universal Analog Input Wiring Figure 5 32 Examples of RTD Input Wiring 124 ...
Page 137: ...137 Figure 5 47 Pulse Outing Wiring Figure 5 48 Frequency Wiring ...
Page 144: ...Figure 5 57 16 point High Level Analog Input Wiring 144 ...
Page 147: ...147 Figure 5 60 AC DC Isolated Input Module Wiring ...
Page 148: ...148 ...
Page 168: ...168 ...
Page 178: ...178 Chapter 8 Diagnostics and Troubleshooting ...
Page 222: ...Appendix A Installing RTP 222 ...
Page 227: ...Appendix A Installing RTP Relay Output RTP Internal schematic 227 ...