n
OFF to ON Response Time: 4 ms maximum with 1.5 lines cycle
maximum
n
ON to OFF Response Time: 4 ms maximum with 2 lines cycle
maximum
n
Power Supply Loading: 5 V: 130 mA max and 24 V: 0 mA
n
RTP support. For more information, see Using an RTP to field
wiring the 16 Point AC DI section.
Digital Input Module (32 channels) - DC Voltage Type
The Digital Input Module-DC Voltage Type is sinking type module with
below features:
n
Channel Density: 32 Channels with two groups of input, each with
a pair of terminals of connection to common
n
Input voltage range: 10 V DC to 32 V DC.
n
Isolation: Galvanic ally isolated in 2 groups of 16 points to rack (30
V DC maximum)
n
ON Voltage Level: 9.5 V DC minimum
n
OFF Voltage Level: 3.5 V DC maximum
n
Minimum ON Current: 1.0 mA
n
Maximum OFF Current: 0.7 mA
n
OFF to ON Response Time: 5 ms maximum
n
ON to OFF Response Time: 5 ms maximum
n
Power Supply Loading: 5 V: 215 mA maximum and 24 V: 0 mA
n
20 pin EURO style terminal block
n
RTP support, 2 RTP are needed for each module. For more
information, see Using Dual RTPs to field wiring the 32 Point DC
DI section.
Relay Output Module (8 Channels)
8 channel electromechanical relay output supports:
n
Channel 1, Channel 2, Channel 7 and Channel 8 are form C type,
provide both NO and NC contact
n
Channel 3 ~ Channel 6 are form A type, provide NO contact.
n
Input Voltage: 120/240 V AC or 30 VDC
n
Output Device: Electromechanical relay; Specified relay life:
1000000 cycles
92
Summary of Contents for ControlEdge 900 platform
Page 6: ...6 Contents ...
Page 12: ...12 Chapter 1 About this guide ...
Page 52: ...52 ...
Page 57: ...57 One Slot Rack 1 CPM 1 EPM 1 P S 1 RM ...
Page 59: ...59 One Slot Rack ...
Page 62: ...Figure 5 7 Rack dimensions with redundant power supply 62 ...
Page 75: ...75 c Insert the Ethernet cables and mount the security cover for the EMP ...
Page 76: ...d Optional mount a wire security seal The user should get a wire security seal themselves 76 ...
Page 124: ...Figure 5 31 Universal Analog Input Wiring Figure 5 32 Examples of RTD Input Wiring 124 ...
Page 137: ...137 Figure 5 47 Pulse Outing Wiring Figure 5 48 Frequency Wiring ...
Page 144: ...Figure 5 57 16 point High Level Analog Input Wiring 144 ...
Page 147: ...147 Figure 5 60 AC DC Isolated Input Module Wiring ...
Page 148: ...148 ...
Page 168: ...168 ...
Page 178: ...178 Chapter 8 Diagnostics and Troubleshooting ...
Page 222: ...Appendix A Installing RTP 222 ...
Page 227: ...Appendix A Installing RTP Relay Output RTP Internal schematic 227 ...