Signal grounding
The shield for each analog input and analog output should be
grounded at the grounding bar at the top or bottom of each rack as
indicated in the following figure. For low-frequency noise rejection,
I/O wiring shields should be grounded only at the ControlEdge 900
Controller end.
Figure 5-19: Wire-signal Grounding for low-frequency noise rejection
For high-frequency noise rejection, shields should be grounded at the
ControlEdge 900 Controller and at the field device. If the ground
voltage potential at the field device is different from that at the
ControlEdge 900 Controller, a DC isolation capacitor (1nf/2000V)
should be used between the shield and the grounding bar on the rack.
Figure 5-20: Wire-signal Grounding for high-frequency noise rejection
Wire shield grounding
Aluminum grounding bars for I/O wiring are available as options.
When selected for use, they are fastened to the top and/or bottom of
each rack, as indicated in the following figure. To enable connection
of multiple ground wires with a single screw, the wires can be twisted
together and secured with a wire lug.
108
Summary of Contents for ControlEdge 900 platform
Page 6: ...6 Contents ...
Page 12: ...12 Chapter 1 About this guide ...
Page 52: ...52 ...
Page 57: ...57 One Slot Rack 1 CPM 1 EPM 1 P S 1 RM ...
Page 59: ...59 One Slot Rack ...
Page 62: ...Figure 5 7 Rack dimensions with redundant power supply 62 ...
Page 75: ...75 c Insert the Ethernet cables and mount the security cover for the EMP ...
Page 76: ...d Optional mount a wire security seal The user should get a wire security seal themselves 76 ...
Page 124: ...Figure 5 31 Universal Analog Input Wiring Figure 5 32 Examples of RTD Input Wiring 124 ...
Page 137: ...137 Figure 5 47 Pulse Outing Wiring Figure 5 48 Frequency Wiring ...
Page 144: ...Figure 5 57 16 point High Level Analog Input Wiring 144 ...
Page 147: ...147 Figure 5 60 AC DC Isolated Input Module Wiring ...
Page 148: ...148 ...
Page 168: ...168 ...
Page 178: ...178 Chapter 8 Diagnostics and Troubleshooting ...
Page 222: ...Appendix A Installing RTP 222 ...
Page 227: ...Appendix A Installing RTP Relay Output RTP Internal schematic 227 ...