4. Secure the field cable in place with a cable tie at top or bottom of
the terminal block. Form a bend in each wire to provide strain
relief, and secure the wire bundle with the tie.
5. Install all I/O modules in the racks.
6. Within each I/O module, install the appropriate terminal block. The
following figure is example, for different modules, the wiring
details are differernt. See "Terminal Block-to-Field (Signal) Wiring"
on the next page for more information.