l
Channel Density: 32 Channels
l
Input voltage range: 10.5 V DC to 32V DC.
l
Isolation: Galvanic ally isolated in 2 groups of 16 channel to rack
l
Overload Current Protection: Active Current Limiting is integrated
into the output driver as 4 groups of 8 channels each. Power
cycling is not required to reset the module after a fault condition.
l
Short Circuit: Whole group of 8 output channels will be switched
off if short circuit happens in any channel of the group. Power
cycling is not required to reset the module.
l
Maximum Load Current:
o
0.5 A per channel;
o
6 A maximum per channel group ;
o
12 A maximum per module;
o
Resistive load 0.25 A per point incandescent lamp load (5 mH
maximum)
o
OFF to ON Response Time*: 6 ms
o
ON to OFF Response Time*: 6 ms
o
Power Supply Loading: 5 V: 235 mA max and 24V: 0 mA
o
20 pin EURO style terminal block
o
RTP support, 2 RTP are needed for each module. For more
information, see Using Dual RTPs to field wiring the 32 Point DC
DO section.
TIP:
*Excluding controllers scan time and excluding
transmission time from module to rack.
Terminal block styles
The terminal block is available in the barrier style, shown below at left
below, and the Euro style, shown at right. Not shown: a Euro style with
36 connections is also available for certain high capacity modules.
Figure 5-18: Terminal block Euro styles
100
Summary of Contents for ControlEdge 900 platform
Page 6: ...6 Contents ...
Page 12: ...12 Chapter 1 About this guide ...
Page 52: ...52 ...
Page 57: ...57 One Slot Rack 1 CPM 1 EPM 1 P S 1 RM ...
Page 59: ...59 One Slot Rack ...
Page 62: ...Figure 5 7 Rack dimensions with redundant power supply 62 ...
Page 75: ...75 c Insert the Ethernet cables and mount the security cover for the EMP ...
Page 76: ...d Optional mount a wire security seal The user should get a wire security seal themselves 76 ...
Page 124: ...Figure 5 31 Universal Analog Input Wiring Figure 5 32 Examples of RTD Input Wiring 124 ...
Page 137: ...137 Figure 5 47 Pulse Outing Wiring Figure 5 48 Frequency Wiring ...
Page 144: ...Figure 5 57 16 point High Level Analog Input Wiring 144 ...
Page 147: ...147 Figure 5 60 AC DC Isolated Input Module Wiring ...
Page 148: ...148 ...
Page 168: ...168 ...
Page 178: ...178 Chapter 8 Diagnostics and Troubleshooting ...
Page 222: ...Appendix A Installing RTP 222 ...
Page 227: ...Appendix A Installing RTP Relay Output RTP Internal schematic 227 ...