ATTENTION: When the DIP switch is set to be off , while the
external power is down, the open wire detection is not available.
n
External Power Source requirement: Vin:18 to 36 VDC
n
Current: 350 mA per module
Digital Input Module-AC DC Voltage type
The AC/DC Input Module provides 16 individually isolated, inputs that
are powered externally. Two terminals are provided for each circuit.
AC or DC power applied between the input terminals cause the inputs
to turn On.
There is a green LED state indicator for each channel on the module
to indicate when a digital input is ON. A green blinking status LED on
the module indicates when the module is being scanned. A red status
LED when module diagnostics exist. Logic in the controller allows the
state to be inverted when necessary. Requires Euro style 36-terminal
terminal block.
*Nominal times excluding controllers scan time and excluding
transmission time from module to rack. DC application must include
controller line filter setting of 50/60 Hz.
Figure 5-17: Active input De-rating table for AC/DC DI
High Level Analog Input Module (16 Channels)
16 user-configurable channel, each channel can be configured as
below type: 0-20 mA
;
4-20 mA
;
0-1 V
;
0-2 V
;
0-5 V
;
0-10 V
;
-1-1
V
;
-2-2 V
;
-5-5 V
;
-10-10 V
Summary of Contents for ControlEdge 900 platform
Page 6: ...6 Contents ...
Page 12: ...12 Chapter 1 About this guide ...
Page 52: ...52 ...
Page 57: ...57 One Slot Rack 1 CPM 1 EPM 1 P S 1 RM ...
Page 59: ...59 One Slot Rack ...
Page 62: ...Figure 5 7 Rack dimensions with redundant power supply 62 ...
Page 75: ...75 c Insert the Ethernet cables and mount the security cover for the EMP ...
Page 76: ...d Optional mount a wire security seal The user should get a wire security seal themselves 76 ...
Page 124: ...Figure 5 31 Universal Analog Input Wiring Figure 5 32 Examples of RTD Input Wiring 124 ...
Page 137: ...137 Figure 5 47 Pulse Outing Wiring Figure 5 48 Frequency Wiring ...
Page 144: ...Figure 5 57 16 point High Level Analog Input Wiring 144 ...
Page 147: ...147 Figure 5 60 AC DC Isolated Input Module Wiring ...
Page 148: ...148 ...
Page 168: ...168 ...
Page 178: ...178 Chapter 8 Diagnostics and Troubleshooting ...
Page 222: ...Appendix A Installing RTP 222 ...
Page 227: ...Appendix A Installing RTP Relay Output RTP Internal schematic 227 ...