111
Item
Hardware Version B
Hardware Version
D/E
AO and DO Channel
Specs
Maximum DO module current 1.5 A. (3
channels at 500 ma or 6 at 250 ma)
Maximum module
current 4.2 A
DI and AI Channel
Specs
Maximum 16 per channel
DO Channel Specs
In 60 Degree C and use High voltage
RTP Cable or Terminal Block
Use High voltage
RTP Cable -
Default :
HART Support
Yes
Certification
CE, UL
CE, UL, FM, CSA,
ATEX, RCM
*The hardware version from View Diagnostics-->I/O diagnostic of
ControlEdge Builder can be found.
Field wiring for Analog Input
The UIO is optimized for use with 2-wire, 3-wire or 4-wire
transmitters. All 16 channels can accept inputs from most 2-wire, 3-
wire or 4-wire transmitters without any special wiring.
The following are the items that UIO AI supports.
n
4-20 mA / 0-20 mA current inputs;
n
Devices that accept external power to power a 0/4-20 mA current
source and (optionally) the device;
n
Devices that return the current to the ground terminal of the
external 24 V power supply;
n
External devices that can moderate non-compliant devices. For
example: 'moderators' = current mirrors, isolators, GI/IS barriers,
mv-to-I.
See the following table for the specification of AI Channel:
Table 5-15: UIO specification of AI Channel
Item
Description
Open wire detection
Configurable and only applicable for 4–20 mA type
Field Voltage
>15 V DC (at 0–24 mA)
Summary of Contents for ControlEdge 900 platform
Page 6: ...6 Contents ...
Page 12: ...12 Chapter 1 About this guide ...
Page 52: ...52 ...
Page 57: ...57 One Slot Rack 1 CPM 1 EPM 1 P S 1 RM ...
Page 59: ...59 One Slot Rack ...
Page 62: ...Figure 5 7 Rack dimensions with redundant power supply 62 ...
Page 75: ...75 c Insert the Ethernet cables and mount the security cover for the EMP ...
Page 76: ...d Optional mount a wire security seal The user should get a wire security seal themselves 76 ...
Page 124: ...Figure 5 31 Universal Analog Input Wiring Figure 5 32 Examples of RTD Input Wiring 124 ...
Page 137: ...137 Figure 5 47 Pulse Outing Wiring Figure 5 48 Frequency Wiring ...
Page 144: ...Figure 5 57 16 point High Level Analog Input Wiring 144 ...
Page 147: ...147 Figure 5 60 AC DC Isolated Input Module Wiring ...
Page 148: ...148 ...
Page 168: ...168 ...
Page 178: ...178 Chapter 8 Diagnostics and Troubleshooting ...
Page 222: ...Appendix A Installing RTP 222 ...
Page 227: ...Appendix A Installing RTP Relay Output RTP Internal schematic 227 ...