n
Channel Used: Any one of the channels can be used for Pulse
Output. However, the use of a particular channel for outputting
pulses will render the particular input channel unusable for either
of pulse, frequency or quadrature input.
n
Digital Output Type: Open Collector, 5 to 24V, 30 mA max
n
Frequency Range: 25 Hz – 10 KHz
n
Duty cycle: Always 50%
n
Pulse Output Duration: Selectable CONTINUOUS or NUMBERED
PULSES.
Frequency Input supports:
n
Input Voltage: 0 V DC to 24V DC
n
ON Voltage Level: 3.0 V DC minimum
n
OFF Voltage Level: 1.0 V DC maximum
n
Input Impedance: 25K ohm
n
Frequency: 10 Hz to 100 KHz
n
Minimum Pulse Width: 500 μsec (10 Hz to 500 Hz) ; 50 μsec (10 Hz
to 5 KHz) ; 2.5 μsec (10 Hz to 100 KHz)
l
The input signal will be rejected if it is below a selected pulse
width.
l
The input signal whose pulse width is above the selected pulse
width must be within the frequency range specified, otherwise a
invalid value (NAN) will be shown and a fail-to-convert error
occurs.
n
Digital Output ON if input frequency out of range, else OFF
Quadrature Input Supports:
n
Channel Used: Only channel 1 and 2 can be used for quadrature
pulses A and B respectively. Index pulse is provided in addition.
n
Input Voltage Range: Differential: -6 VDC to +6 VDC; Single-ended:
0 VDC to 24 VDC
n
ON Voltage Level: Differential: 0.2 VDC minimum; Single-ended:
3.0 VDC minimum
n
OFF Voltage Level: Differential: -0.2 VDC maximum; Single-ended:
1 VDC maximum
n
Common Mode Voltage: +/- 12VDC
n
Input Sensitivity: +/- 200mV
n
Hysteresis: +/- 50mV
n
Module powered encoder: 5V DC, 0.50A
n
Frequency: 200 KHz maximum
94
Summary of Contents for ControlEdge 900 platform
Page 6: ...6 Contents ...
Page 12: ...12 Chapter 1 About this guide ...
Page 52: ...52 ...
Page 57: ...57 One Slot Rack 1 CPM 1 EPM 1 P S 1 RM ...
Page 59: ...59 One Slot Rack ...
Page 62: ...Figure 5 7 Rack dimensions with redundant power supply 62 ...
Page 75: ...75 c Insert the Ethernet cables and mount the security cover for the EMP ...
Page 76: ...d Optional mount a wire security seal The user should get a wire security seal themselves 76 ...
Page 124: ...Figure 5 31 Universal Analog Input Wiring Figure 5 32 Examples of RTD Input Wiring 124 ...
Page 137: ...137 Figure 5 47 Pulse Outing Wiring Figure 5 48 Frequency Wiring ...
Page 144: ...Figure 5 57 16 point High Level Analog Input Wiring 144 ...
Page 147: ...147 Figure 5 60 AC DC Isolated Input Module Wiring ...
Page 148: ...148 ...
Page 168: ...168 ...
Page 178: ...178 Chapter 8 Diagnostics and Troubleshooting ...
Page 222: ...Appendix A Installing RTP 222 ...
Page 227: ...Appendix A Installing RTP Relay Output RTP Internal schematic 227 ...