119
A 15K shunt resistor and a 7.5K series resistor are required closed to
the contact in field side. Refer to the following block diagram of this
channel configuration, and a field wiring example.
ATTENTION:
For Channels that are configured with a debounce, the UIO will
declare that the channel has changed state if all the
consecutive samples are in the new state for the configured
debounce time period.
Field wiring for Digital Output
When UIO is configured as a Digital Output, the channel can supply
up to 0.5A to the field. See the following table for the specification of
DO.
Table 5-18: UIO Specification for DO
Item
Description
Open wire detection
Configurable
Short circuit detection
Enabled by default and un-configurable
Maximum (resistive Load)
500mA
Minimum Load
20mA with OWD and 0mA without OWD
Maximum load capacitance
1 uF
Voltage Drop
< 1 V (at 500mA)
Off Current
< 0.1mA
Lead breakage test current
Approx. 10 mA
Output Current
0 - 23 mA
TIP:
If a Universal I/O Channel configured as Digital Output reports
an “OP Fail in circuit/field wire” alarm, the most likely cause of
the alarm is a broken wire. The user should check the continuity
of field wiring. It is suggested to enable Line Monitoring for
DOs so that the Event Log can clearly identify the problem as a
possible wire break.
Summary of Contents for ControlEdge 900 platform
Page 6: ...6 Contents ...
Page 12: ...12 Chapter 1 About this guide ...
Page 52: ...52 ...
Page 57: ...57 One Slot Rack 1 CPM 1 EPM 1 P S 1 RM ...
Page 59: ...59 One Slot Rack ...
Page 62: ...Figure 5 7 Rack dimensions with redundant power supply 62 ...
Page 75: ...75 c Insert the Ethernet cables and mount the security cover for the EMP ...
Page 76: ...d Optional mount a wire security seal The user should get a wire security seal themselves 76 ...
Page 124: ...Figure 5 31 Universal Analog Input Wiring Figure 5 32 Examples of RTD Input Wiring 124 ...
Page 137: ...137 Figure 5 47 Pulse Outing Wiring Figure 5 48 Frequency Wiring ...
Page 144: ...Figure 5 57 16 point High Level Analog Input Wiring 144 ...
Page 147: ...147 Figure 5 60 AC DC Isolated Input Module Wiring ...
Page 148: ...148 ...
Page 168: ...168 ...
Page 178: ...178 Chapter 8 Diagnostics and Troubleshooting ...
Page 222: ...Appendix A Installing RTP 222 ...
Page 227: ...Appendix A Installing RTP Relay Output RTP Internal schematic 227 ...