CAUTION:
Hazardous voltages
exist at terminal blocks.
Using switches at field devices disconnect the field wiring form
power sources before servicing.
Failure to comply with these instructions could result in death or
serious injury.
If installing 8 channel Analog Output module, set its DIP switch as
follows. (Switch is located at edge of module, marked “SW1”.)
n
For internal rack power, set DIP switch to ON.
n
For external power (18-36V), set DIP switch to OFF (default).
NOTE: 24VDC external power is required if using 6 or more 8-pt.
AO modules or 3 or more 16-pt. AO modules.
A small slotted screwdriver or paperclip works well; avoid using
pencils.
Figure 5-54: Dip Swith Position of 8 Channel AO
Figure 5-55: 8 Channel Analog Output Wiring Diagram
142
Summary of Contents for ControlEdge 900 platform
Page 6: ...6 Contents ...
Page 12: ...12 Chapter 1 About this guide ...
Page 52: ...52 ...
Page 57: ...57 One Slot Rack 1 CPM 1 EPM 1 P S 1 RM ...
Page 59: ...59 One Slot Rack ...
Page 62: ...Figure 5 7 Rack dimensions with redundant power supply 62 ...
Page 75: ...75 c Insert the Ethernet cables and mount the security cover for the EMP ...
Page 76: ...d Optional mount a wire security seal The user should get a wire security seal themselves 76 ...
Page 124: ...Figure 5 31 Universal Analog Input Wiring Figure 5 32 Examples of RTD Input Wiring 124 ...
Page 137: ...137 Figure 5 47 Pulse Outing Wiring Figure 5 48 Frequency Wiring ...
Page 144: ...Figure 5 57 16 point High Level Analog Input Wiring 144 ...
Page 147: ...147 Figure 5 60 AC DC Isolated Input Module Wiring ...
Page 148: ...148 ...
Page 168: ...168 ...
Page 178: ...178 Chapter 8 Diagnostics and Troubleshooting ...
Page 222: ...Appendix A Installing RTP 222 ...
Page 227: ...Appendix A Installing RTP Relay Output RTP Internal schematic 227 ...