3 NAMES AND FUNCTIONS OF PARTS
- 25 -
No.
Name
Function
①
Power indicating LED
(POWER)
Lights when the power switch is turned on.
②
Voltage check terminal
(DC5V)
Checks the voltage of the 5 V output. (Normal: 4.75 to 5.25 V)
(Do not use this terminal for other than voltage check.)
③
Voltage check terminal
(GND)
Check the 0 V reference voltage.
(Do not use this terminal for other than voltage check.)
④
Power switch
(POWER)
Turns on or off the power input to the power supply module.
⑤
Power supply terminal block
(H, N)
Supplies input power to the power supply module.
The input voltage varies with each type of power supply module.
⑥
Line filter ground terminal (LG)
Ground terminal for the power supply line filter. Connected to the enclosure (unit)
ground.
⑦
Frame ground terminal (FG)
Connected to the mount base FG terminal or to a single-point ground plate.
CAUTION
To avoid possible failures, allow for at least one second between turning-on and
turning-off of the power switch.
Summary of Contents for S10mini D
Page 1: ......
Page 14: ...THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 19: ...1 BEFORE USE ...
Page 28: ...THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 29: ...2 OVERVIEW ...
Page 34: ...THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 35: ...3 NAMES AND FUNCTIONS OF PARTS ...
Page 45: ...4 INSTALLATION ...
Page 54: ...THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 55: ...5 WIRING ...
Page 68: ...THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 69: ...6 SETTING ...
Page 84: ...THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 85: ...7 OPERATION PROCEDURES ...
Page 91: ...8 EXPLANATION OF OPERATION ...
Page 111: ...9 MAINTENANCE ...
Page 128: ...THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 129: ...10 SPECIFICATIONS ...