Register
No.
Function name
Function
code
R/W
Monitoring and setting items
Data
resolution
1342h to
1348h (Reserved) -
-
-
1349h Operation level at O
disconnection
b070 R/W
0. to 100. (%) or "no" (ignore)
1 [%]
134Ah to
1350h (reserved) -
-
-
-
1351h
Cumulative input power data
clearance
b078
R/W Clearance by setting "1"
-
1352h Watt-hour display gain
b079
R/W 1 to 1000
1
1353h to
1354h (Reserved) -
-
-
-
1355h Start frequency
b082
R/W 1 to 999
0.01 [Hz]
1356h Carrier frequency
b083
R/W 20 to 150
0.1 [kHz]
1357h Initialization mode (parameters or
trip history)
b084 R/W
0(disabling),1 (clearing the trip history),
2 (initializing the data), 3 (clearing the
trip history and initializing the data)
-
1358h Country code for initialization
b085
R/W 0 (area A), 1 (area B), 3(area D)
-
1359h Frequency scaling conversion
factor
b086
R/W 1 to 9999
0.01
135Ah STOP key enable
b087
R/W
0 :ON(enabling),
1 :OFF (disabling),
2 :Only Reset(disabling only stop)
-
135Bh Restart mode after FRS
b088
R/W 0 (starting with 0 Hz), 1 (starting with
matching frequency)
-
135Ch
Automatic carrier frequency
reduction
b089 R/W
0(disabling)/1(enabling( output current
controlled))
-
135Dh (Reserved)
-
-
-
-
135Eh Stop mode selection
b091
R/W 0 (deceleration until stop), 1 (free-run
stop)
-
135Fh (Reserved)
-
-
-
-
1360h (Reserved) -
-
-
-
1361h
Initialization target data
b094 R/W
0(All parameter)
/1(expect terminal and communication
)
-
1362h to
1366h (Reserved) -
-
-
-
1367h Free-setting V/f frequency (1)
b100
R/W 0. to "free-setting V/f frequency (2)"
1 [Hz]
1368h Free-setting V/f voltage (1)
b101
R/W 200V:0. to 3000 400 V:0. to 6000
0.1 [V]
1369h Free-setting V/f frequency (2)
b102
R/W 0. to "free-setting V/f frequency (3)"
1 [Hz]
136Ah Free-setting V/f voltage (2)
b103
R/W 200V:0. to 3000 400 V:0. to 6000
0.1 [V]
136Bh Free-setting V/f frequency (3)
b104
R/W 0. to "free-setting V/f frequency (4)"
1 [Hz]
136Ch Free-setting V/f voltage (3)
b105
R/W 200V:0. to 3000 400 V:0. to 6000
0.1 [V]
136Dh Free-setting V/f frequency (4)
b106
R/W 0. to "free-setting V/f frequency (5)"
1 [Hz]
136Eh Free-setting V/f voltage (4)
b107
R/W 200V:0. to 3000 400 V:0. to 6000
0.1 [V]
136Fh Free-setting V/f frequency (5)
b108
R/W 0. to "free-setting V/f frequency (6)"
1 [Hz]
1370h Free-setting V/f voltage (5)
b109
R/W 200V:0. to 3000 400 V:0. to 6000
0.1 [V]
1371h Free-setting V/f frequency (6)
b110
R/W 0. to "free-setting V/f frequency (7)"
1 [Hz]
1372h Free-setting V/f voltage (6)
b111
R/W 200V:0. to 3000 400 V:0. to 6000
0.1 [V]
1373h Free-setting V/f frequency (7)
b112
R/W 0. to 400.
1 [Hz]
1374h Free-setting V/f voltage (7)
b113
R/W 200V:0. to 3000 400 V:0. to 6000
0.1 [V]
Summary of Contents for NES1-002LB
Page 9: ......
Page 21: ......
Page 25: ......
Page 28: ...Chapter 3 Exterior Views 3 3 ...
Page 30: ......
Page 35: ......
Page 53: ......
Page 75: ......
Page 154: ......
Page 196: ......
Page 203: ...Chapter 10 Troubleshooting This chapter describes the troubleshooting methods ...
Page 204: ......
Page 211: ......
Page 219: ......
Page 229: ......
Page 289: ...Appendix Appendix A Appendix A 1 ...
Page 290: ......
Page 292: ...Appendix Appendix 2 ...