Chapter 7 Explanation of Functions
7 - 21
(3) Free V/f characteristic setting
The free V/f characteristic setting function allows you to set an arbitrary V/f characteristic by specifying the
voltages and frequencies (b100 to b113) for the seven points on the V/f characteristic curve.
The free V/f frequencies (1 to 7) set by this function must always be in the collating sequence of "1
≤
2
≤
3
≤
4
≤
5
≤
6
≤
7".
Since all free V/f frequencies are set to 0 Hz as default (factory setting), specify their arbitrary values
(begin setting with free-setting V/f frequency (7)). (The inverter cannot operate with the free V/f
characteristic in the factory setting.)
Enabling the free V/f characteristic setting function disables the torque boost selection (A041/A241), base
frequency setting (A003/A203), and maximum frequency setting (A004/A204). (The inverter assumes the
value of free-setting V/f frequency (7) as the maximum frequency.)
Item Function
code
Data
Description
Free-setting V/f frequency (7)
b112
0.to 400.(Hz)
Setting of the output
frequency at each
breakpoint of the V/f
characteristic curve
Free-setting V/f frequency (6)
b110
0. to free-setting V/f frequency (7) (Hz)
Free-setting V/f frequency (5)
b108
0. to free-setting V/f frequency (6) (Hz)
Free-setting V/f frequency (4)
b106
0. to free-setting V/f frequency (5) (Hz)
Free-setting V/f frequency (3)
b104
0. to free-setting V/f frequency (4) (Hz)
Free-setting V/f frequency (2)
b102
0. to free-setting V/f frequency (3) (Hz)
Free-setting V/f frequency (1)
b100
0. to free-setting V/f frequency (2) (Hz)
Free-setting V/f voltage (7)
b113
0.0 to 300.0(V) :Selectable on 200 V
class inverter models
0.0 to 600.0(V) :Selectable on 400 V
class inverter models
Setting of the output
voltage at each
breakpoint of the V/f
characteristic curve (*1)
Free-setting V/f voltage (6)
b111
Free-setting V/f voltage (5)
b109
Free-setting V/f voltage (4)
b107
Free-setting V/f voltage (3)
b105
Free-setting V/f voltage (2)
b103
Free-setting V/f voltage (1)
b101
(Example)
*1 Even if 300 V is set as a free-setting V/f voltage (1 to 7), the inverter output voltage cannot exceed the
inverter input voltage or that specified by the AVR voltage select.
Carefully note that selecting an inappropriate control system (V/f characteristic) may result in
overcurrent during motor acceleration or deceleration or vibration of the motor or other machine driven
by the inverter.
f1
f2
f3
f4
f5
f6
f7
0
V2,V3
V1
V5
V6
V7
V4
Output voltage (V)
Output frequency (Hz)
0
f6
f7
V6
V7
Voltage that can be output by the
inverter or that was specified by
the AVR voltage select
Output frequency (Hz)
Output voltage (V)
Summary of Contents for NES1-002LB
Page 9: ......
Page 21: ......
Page 25: ......
Page 28: ...Chapter 3 Exterior Views 3 3 ...
Page 30: ......
Page 35: ......
Page 53: ......
Page 75: ......
Page 154: ......
Page 196: ......
Page 203: ...Chapter 10 Troubleshooting This chapter describes the troubleshooting methods ...
Page 204: ......
Page 211: ......
Page 219: ......
Page 229: ......
Page 289: ...Appendix Appendix A Appendix A 1 ...
Page 290: ......
Page 292: ...Appendix Appendix 2 ...