Chapter 7 Explanation of Functions
7 - 57
7.7.4 Unattended start protection (USP) function
The unattended start protection function allows you to make the inverter trip with error code "E13"
displayed if the inverter power is turned on when an operation command has been turned on.
You can recover the inverter from tripping by performing the reset operation or turning the operation
command off. (See example 1.)
If the inverter is recovered from tripping with the operation command left turned on, the inverter will start
operation immediately after recovery. (See example 2.)
The inverter can operate normally when an operation command is turned on after the inverter power is
turned on. (See example 3.)
To use this function, assign function "13" (USP) to one of the terminal [1] to [5] functions (C001 to C005).
This function is invalid with the standard operation panel (RUN/STOP/RESET key).
When it is input a run command from the operator or Modbus within two seconds after the power supply
injection, the inverter trip(E13).
The following charts show examples of the timing of the unattended start protection operation:
(Example 1)
(Example 2)
(Example 3)
Item Function
code
Data
Description
Terminal [1] to [5] functions
C001 to C005
13
USP: Unattended start protection
Power
supply
FW
USP
RS
Alarm
Output
frequency
Power
supply
FW
USP
RS
Alarm
Output
frequency
Power
supply
FW
USP
RS
Alarm
Output
frequency
Summary of Contents for NES1-002LB
Page 9: ......
Page 21: ......
Page 25: ......
Page 28: ...Chapter 3 Exterior Views 3 3 ...
Page 30: ......
Page 35: ......
Page 53: ......
Page 75: ......
Page 154: ......
Page 196: ......
Page 203: ...Chapter 10 Troubleshooting This chapter describes the troubleshooting methods ...
Page 204: ......
Page 211: ......
Page 219: ......
Page 229: ......
Page 289: ...Appendix Appendix A Appendix A 1 ...
Page 290: ......
Page 292: ...Appendix Appendix 2 ...