Chapter 13 Option
13 - 22
“C” Function
Run
Mode
Edit
Defaults
Func.
Code
Name
Description
Initial data
standard
200/400
Initial data
CHN
200/400
Initial data
EU
200/400
Units
C152
Scroll sensitivity
selection
1 to 20
10
←
←
C155
Ground fault
detection
00(OFF) / 01(ON)
01
←
←
C157
Out phase loss
detection
00(OFF) / 01(ON)
00
←
←
C160
Input [1] response
time
Sets response time of each input
terminal, set range:
0(x 2 [ms]) to 200(x 2 [ms])
(0 to 400 [ms])
1.
←
←
C161
Input [2] response
time
1.
←
←
C162
Input [3] response
time
1.
←
←
C163
Input [4] response
time
1.
←
←
C164
Input [5] response
time
1.
←
←
C169
Multistage speed
determination time
Set range is 0. to 200. (x 10ms)
0.
←
←
ms
“H” Function
Run
Mode
Edit
Defaults
Func.
Code
Name
Description
Initial data
standard
200/400
Initial data
CHN
200/400
Initial data
EU
200/400
Units
H003
Motor capacity
Twelve selections:
0.10/0.20/0.40/0.55/0.75/1.10/1.50
/2.20/3.00/3.70/4.00/5.50
Specified
by the
capacity
of each
inverter
model
←
←
kW
H203
Motor capacity,
2
nd
motor
←
←
kW
H004
Motor poles
setting
Five selections:
2 / 4 / 6 / 8
4
←
←
poles
H204
Motor poles
setting,
2
nd
motor
4
←
←
poles
H006
Motor stabilization
constant
Motor constant (factory set),
range is 0 to 255
100.
←
←
H206
Motor stabilization
constant, 2
nd
motor
100.
←
←
Summary of Contents for NES1-002LB
Page 9: ......
Page 21: ......
Page 25: ......
Page 28: ...Chapter 3 Exterior Views 3 3 ...
Page 30: ......
Page 35: ......
Page 53: ......
Page 75: ......
Page 154: ......
Page 196: ......
Page 203: ...Chapter 10 Troubleshooting This chapter describes the troubleshooting methods ...
Page 204: ......
Page 211: ......
Page 219: ......
Page 229: ......
Page 289: ...Appendix Appendix A Appendix A 1 ...
Page 290: ......
Page 292: ...Appendix Appendix 2 ...