Chapter 13 Option
13 - 14
“b” Function
Run
Mode
Edit
Defaults
Func.
Code
Name
Description
Initial data
standard
200/400
Initial data
CHN
200/400
Initial data
EU
200/400
Units
b031
Software
lock
mode
selection
Prevents parameter changes, in five options,
option codes:
00
all parameters except b031 are locked
when [SFT] terminal is ON
01
all parameters except b031 and output
frequency F001 are locked
when [SFT] terminal is ON
02
all parameters except b031 are locked
03
all parameters except b031 and output
frequency F001 are locked
10
High level access including b031
See appendix C for the accessible
parameters in this mode.
01
10 01
b034
Run/pow
er ON
warning
time
Range is,
0.:Warning disabled
1. to 9999.:
10~99,990 hrs (unit: 10)
1000 to 6553:
100,000~655,350 hrs (unit: 100)
0.
←
←
Hrs.
b035
Rotation
direction
restriction
Three option codes:
00
No restriction
01
Reverse rotation is restricted
02
Forward rotation is restricted
00
←
←
b036
Reduced
voltage
start
selection
Set range, 0 (disabling the function), 1 (approx.
4ms) to 250 (approx. 1s)
3
←
←
b037
Function
code
display
restriction
Five option codes:
00
Full display
01
Function-specific display
03
Data comparison display
04
Basic display
05
Monitor display only
00
←
←
b038
Initial
display
selection
000
Func. code that SET key pressed last
displayed.(*)
001~060
d001~d060 displayed
201
F001displayed
202
B display of LCD operator
(In case of Digital operator, same 000
setting)
001
←
←
b050
Controlle
d
decelerati
on on
power
loss
Four option codes:
00
Disabled
01
Decelerates to a stop
02
Decelerates to a stop with DC bus voltage
controlled
03
Decelerates to a stop with DC bus voltage
controlled, then restart
00
←
←
b051
DC bus
voltage
trigger
level of
ctrl.
decel.
Setting of DC bus voltage to start controlled
decel. operation. Range is 0.0 to 400.0(200V
class inverter settings),0.0 to 800(400V class
inverter settings)
220.0/
440.0
←
←
V
b052
Over-volt
age
threshold
of ctrl.
decel.
Setting the OV-LAD stop level of controlled
decel. operation. Range is 0.0 to 400.0(200V
class inverter settings),0.0 to 800(400V class
inverter settings)
360.0/
720.0
←
←
V
Summary of Contents for NES1-002LB
Page 9: ......
Page 21: ......
Page 25: ......
Page 28: ...Chapter 3 Exterior Views 3 3 ...
Page 30: ......
Page 35: ......
Page 53: ......
Page 75: ......
Page 154: ......
Page 196: ......
Page 203: ...Chapter 10 Troubleshooting This chapter describes the troubleshooting methods ...
Page 204: ......
Page 211: ......
Page 219: ......
Page 229: ......
Page 289: ...Appendix Appendix A Appendix A 1 ...
Page 290: ......
Page 292: ...Appendix Appendix 2 ...