Chapter 13 Option
13 - 51
Input Function Summary Table
– This table shows all thirty-four intelligent input functions at a glance.
Detailed description of these functions, related parameters and settings, and example wiring diagrams are
in “Using Intelligent Input Terminals” on page 4-8.
Input Function Summary Table
Option
Code
Terminal
Symbol
Function Name
Description
00
FW
FORWARD
Run/Stop
ON
Inverter is in Run Mode, motor runs forward
OFF
Inverter is in Stop Mode, motor stops
01
RV Reverse
Run/Stop
ON
Inverter is in Run Mode, motor runs reverse
OFF
Inverter is in Stop Mode, motor stops
02
CF1 *1
Multi-speed Select,
Bit 0 (LSB)
ON
Binary encoded speed select, Bit 0, logical 1
OFF
Binary encoded speed select, Bit 0, logical 0
03
CF2
Multi-speed Select,
Bit 1
ON
Binary encoded speed select, Bit 1, logical 1
OFF
Binary encoded speed select, Bit 1, logical 0
04
CF3
Multi-speed Select,
Bit 2(MSB)
ON
Binary encoded speed select, Bit 2, logical 1
OFF
Binary encoded speed select, Bit 2, logical 0
06
JG Jogging
ON
Inverter is in Run Mode, output to motor runs at jog
parameter frequency
OFF
Inverter is in Stop Mode
07
DB
External DC braking
ON
DC braking will be applied during deceleration
OFF
DC braking will not be applied
08
SET
Set (select) 2nd
Motor Data
ON
The inverter uses 2nd motor parameters for
generating frequency output to motor
OFF
The inverter uses 1st (main) motor parameters for
generating frequency output to motor
09
2CH
2-stage Acceleration
and Deceleration
ON
Frequency output uses 2nd-stage acceleration and
deceleration values
OFF
Frequency output uses standard acceleration and
deceleration values
11
FRS Free-run
Stop
ON
Causes output to turn OFF, allowing motor to free
run (coast) to stop
OFF
Output operates normally, so controlled deceleration
stop motor
12
EXT External
Trip
ON
When assigned input transitions OFF to ON, inverter
latches trip event and displays
OFF
No trip event for ON to OFF, any recorded trip
events remain in history until reset
13
USP
Unattended Start
Protection
ON
On power up, the inverter will not resume a Run
command (mostly used in the US)
OFF
On power up, the inverter will resume a Run
command that was active before power loss
15
SFT Software
Lock
ON
The keypad and remote programming devices are
prevented from changing parameters
OFF
The parameters may be edited and stored
18
RS Reset
Inverter
ON
The trip condition is reset, the motor output is turned
OFF, and power up reset is asserted
OFF
Normal power-ON operation
20
STA
Start
(3-wire interface)
ON
Starts the motor rotation
OFF
No change to present motor status
21
STP
Stop
(3-wire interface)
ON
Stops the motor rotation
OFF
No change to present motor status
22
F/R
FWD, REV
(3-wire interface)
ON
Selects the direction of motor rotation: ON = FWD.
While the motor is rotating, a change of F/R will start
a deceleration, followed by a change in direction
OFF
Selects the direction of motor rotation: OFF = REV.
While the motor is rotating, a change of F/R will start
a deceleration, followed by a change in direction
Summary of Contents for NES1-002LB
Page 9: ......
Page 21: ......
Page 25: ......
Page 28: ...Chapter 3 Exterior Views 3 3 ...
Page 30: ......
Page 35: ......
Page 53: ......
Page 75: ......
Page 154: ......
Page 196: ......
Page 203: ...Chapter 10 Troubleshooting This chapter describes the troubleshooting methods ...
Page 204: ......
Page 211: ......
Page 219: ......
Page 229: ......
Page 289: ...Appendix Appendix A Appendix A 1 ...
Page 290: ......
Page 292: ...Appendix Appendix 2 ...