Chapter 8 Communication Functions
8 - 19
8.8 Modbus Data Listing
(A) Modbus Coil List
The following tables list the primary coils for the inverter interface to the network. The table legend
is given below.
Coil No. -
The network
register address offset
for the coil. The coil data is a single bit (binary)
value.
Item -
The functional name of the coil
R/W -
The read-only (R) or read-write (R/W) access permitted to the inverter data
Setting -
The meaning of each of the states of the coils
Coil
No.
Item
R/W
Setting
0000h unused
-
(Inaccessible)
0001h
Operation command
R/W
1: Run, 0: Stop (valid when A002/A202 = 03)
0002h
Rotation direction command
R/W
1: Reverse rotation, 0: Forward rotation (valid when
A002/A202 = 03)
0003h
External trip (EXT)
R/W
1: Trip
0004h
Trip reset (RS)
R/W
1: Reset
0005h (Reserved)
-
-
0006h (Reserved)
-
-
0007h
Intelligent input terminal [1]
R/W
1: ON, 0: OFF (*1)
0008h
Intelligent input terminal [2]
R/W
1: ON, 0: OFF (*1)
0009h
Intelligent input terminal [3]
R/W
1: ON, 0: OFF (*1)
000Ah
Intelligent input terminal [4]
R/W
1: ON, 0: OFF (*1)
000Bh
Intelligent input terminal [5]
R/W
1: ON, 0: OFF (*1)
000Ch to
000Eh
(Reserved)
- -
000Fh
Operation status
R
1: Run, 0: Stop (interlocked to "d003")
0010h
Rotation direction
R
1: Reverse rotation, 0: Forward rotation (interlocked to
"d003")
0011h
Inverter ready (IRDY)
R
1: Ready, 0: Not ready (Same as Coil No.0045h)
0012h (Reserved)
-
-
0013h
RUN (running)
R
1: ON, 0: OFF
0014h
FA1 (constant-speed reached)
R
1: ON, 0: OFF
0015h
FA2 (set frequency overreached)
R
1: ON, 0: OFF
0016h
OL (overload advance notice (1))
R
1: ON, 0: OFF
0017h
OD (output deviation for PID control)
R
1: ON, 0: OFF
0018h
AL (alarm signal)
R
1: ON, 0: OFF
0019h
FA3 (set frequency reached)
R
1: ON, 0: OFF
001Ah (Reserved)
-
-
001Bh (Reserved)
-
-
001Ch
UV (undervoltage)
R
1: ON, 0: OFF
001Dh (Reserved)
-
-
001Eh
RNT (operation time over)
R
1: ON, 0: OFF
001Fh
ONT (plug-in time over)
R
1: ON, 0: OFF
0020h
THM (thermal alarm signal)
R
1: ON, 0: OFF
0021h to
0027h
(Reserved)
- -
0028h
ZS (0 Hz detection signal)
R
1: ON, 0: OFF
0029h to
002Dh
(Reserved)
- -
Summary of Contents for NES1-002LB
Page 9: ......
Page 21: ......
Page 25: ......
Page 28: ...Chapter 3 Exterior Views 3 3 ...
Page 30: ......
Page 35: ......
Page 53: ......
Page 75: ......
Page 154: ......
Page 196: ......
Page 203: ...Chapter 10 Troubleshooting This chapter describes the troubleshooting methods ...
Page 204: ......
Page 211: ......
Page 219: ......
Page 229: ......
Page 289: ...Appendix Appendix A Appendix A 1 ...
Page 290: ......
Page 292: ...Appendix Appendix 2 ...